Assembly and wiring
20
4.4 Port assignments
Technical manual LioN-Link BusHead EtherNet/IP™
Release 1.1 04/2016
Figure 4: Port assignment LioN Link
4.4.4
Addressing window
Configure the IP address manually using the 3 encoding dials in the
addressing window (see
).
4.4.5
EtherNet
M12 socket, 4-pin, D-coded
Color coding: mint green
Pin
Signal
Function
1
DRAIN
Shield
2
+24V DC
Subbus line 1 or 2 – module power
3
0V GND
Subbus line 1 or 2 – module power supply -
4
DATA+
LioN Link data communi
5
DATA-
LioN Link data communication -
Table 5:
Port assignment LioN Link
NOTE
All M12 metal sleeves are electrically connection via functional ground.