Control 1.3 Swimming Pool Control Unit
Operation
31
A14 (speed 3-increased, potential-free N/O contact)
A15 (speed 1-reduced, potential-free N/O contact)
A16 (stop signal, potential-free switch)
A18 (percentage speed, standard signal 0-10 V)
6.4.3.5
Flow Switch
You need to go to the
Treatment
Flow Switch
submenu to set a flow switch. This is shown in Figure 6.
Figure 6: Flow switch
-
Flow switch: defines whether a flow switch has been connected
-
Forced pump: defines whether the filter pump should be stopped in the case of an error message
from the flow switch.
-
Type: defines the switching mode of the flow switch (N/O contact or N/C contact)
-
Delay: defines the time until the control unit emits an error message due to the input signal from the
flow switch.
The flow switch must be connected to the terminal E6.
6.4.3.6
Level Control (Setting)
You need to go to the
Treatment
Level Control
submenu to set the level control. This is shown in
-
Pool type: defines whether the pool is a skimmer or overflow pool. A Behncke level control (art no.
39019095) is required as an add-on module for overflow pools.
-
Fill valve: defines whether a fill valve (solenoid valve) is connected
-
Type: only available for skimmer pools. Defines the switching mode of the float switch (N/O contact
or N/C contact)
-
Delay: defines the time until the control unit controls the fill valve due to an input signal.
-
Dosing technology: defines whether the dosing technology is deactivated for the time during which
the fill valve is activated.
Содержание Control 1.3
Страница 18: ...Control 1 3 Swimming Pool Control Unit Technical Data 16 ...
Страница 50: ...Control 1 3 Swimming Pool Control Unit Notes 48 Notes ...
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......