RCD– Reacting time
Load time:
300 ms with 1/3 of selcted nominal fault current
300 ms with nominal fault current
Test time:
ca. 4 s
Limit value for reacting time :
300 ms
Accuracy of limit value:
+0 %, -10 %
Rotary field
Voltage range:
175 V ... 415 V (between the phases)
Frequency:
50 ... 60 Hz
Max. different of
phase voltage:
± 15 %
General
Display:
LCD with additional red and green LED
Battery type:
6 x 1,5 V, IEC LR6, Mignon, Type AA
Current consumption:
ca. 20 mA (standby)
Battery life time:
at average use approx. 1year
Auto-Power-Off:
approx. 5 min
Fuse:
2 pcs F 500 mA / 500 V, 6,3 x 32 mm
Case:
Safety class II
Maximum rating voltage:
500 V AC/DC
Over voltage category:
CAT III / 440 V against ground
According to:
DIN VDE 0413, part 1, 2, 3, 4, 6, 7, 10
EN 61557, part 1, 2, 3, 4, 6, 7, 10
IEC 61557, part 1, 2, 3, 4, 6, 7, 10
DIN VDE 0411, part 1
EN 61010, part 1
IEC 61010, part 1
Degree of contamination:
2
Protection class:
IP50
Dimensions (LxWxH):
235 x 105 x 68 mm
Weight:
ca. 660 g incl. batteries
Ambient Conditions
Reference temperature range:
+17°C...22 ...27°C, max. 70% rel. humidity
Operation temperature range:
0 °C...+40 °C, max. 80% relative humidity without dewfall
Storage temperature range:
-10 °C...+60 °C, max. 80% relative humidity without dewfall
Height above MSL:
up to 2000 m