4–83
System Setup and Setpoints – 4
59 Phase Overvoltage
The Phase
Overvoltage function (59) may be used
to provide overvoltage protection for the generator.
The relay provides overvoltage protection functions
with three voltage levels and three definite-time
setpoints, any one or more of which can be
programmed to trip the unit or send an alarm. This
is a true 3-phase function in that each phase has
an independent timing element.
The 59 function can be programmed to use phase
voltage (any one of the three phases) or positive
sequence voltage as input.
Positive and negative sequence voltages are
calculated in terms of line-to-line voltage when Line
to Line is selected for V.T. Configuration.
V
1
= 1/3
(V
ab
+aV
bc
+ a
2
V
ca
)
V
2
= 1/3
(V
ab
+a
2
V
bc
+ aV
ca
)
Magnitude measurement depends on the 59/27
Magnitude Select setting (See Section 4.2 Setup
System). When the RMS option is selected, the
magnitude calculation is accurate over a wide
frequency range (10 to 80 Hz) and the accuracy
of the time delay is +20 cycles. If DFT option is
selected, the magnitude calculation is accurate near
50 or 60 Hz, and the timer accuracy is +1 cycle.
When the input voltage select is set to positive
sequence voltage, the 59 functions uses DFT to
measure the positive sequence voltage, irrespective
of DFT/RMS selection. Ranges and increments are
presented in Figure 4-62.
Generator capability is generally 105% of rated voltage.
59 #2 and 59 #3 screens are identical to 59 #1.
59 #1 INPUT VOLTAGE SEL.
phase_volt pos_seq_volt
59 #1 PICKUP
Volts
59 #1 DELAY
Cycles
Содержание M-3425A
Страница 1: ...Instruction Book M 3425A Generator Protection ...
Страница 38: ...This Page Left Intentionally Blank ...
Страница 39: ...800 3425A SP 10MC2 07 12 2001 Beckwith Electric Co All Rights Reserved Printed in U S A 01 67 04 25 03 ...
Страница 43: ...This Page Left Intentionally Blank ...
Страница 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Страница 73: ...M 3425A Instruction Book 2 10 Path Monitor Primary Metering Status Figure 2 4 Primary Metering Status Screen ...
Страница 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Страница 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Страница 103: ...M 3425A Instruction Book 3 8 Path Monitor Primary Metering and Status Figure 3 9 Primary Metering Status Screen ...
Страница 105: ...M 3425A Instruction Book 3 10 Path Monitor Secondary Metering and Status Figure 3 10 Secondary Metering Status Screen ...
Страница 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Страница 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Страница 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Страница 180: ...4 49 System Setup and Setpoints 4 Table 4 5 Impedance Calculation Figure 4 30 Phase Distance 21 Setpoint Ranges ...
Страница 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Страница 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Страница 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Страница 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Страница 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Страница 219: ...4 88 M 3425A Instruction Book Figure 4 65 Overvoltage Neutral Circuit or Zero Sequence 59N Setpoint Ranges ...
Страница 236: ...4 105 System Setup and Setpoints 4 Figure 4 77 Residual Directional Overcurrent 67N Setpoint Ranges ...
Страница 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Страница 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Страница 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Страница 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Страница 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Страница 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Страница 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Страница 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Страница 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Страница 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Страница 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Страница 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Страница 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Страница 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Страница 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Страница 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Страница 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Страница 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Страница 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Страница 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 481: ...This Page Left Intentionally Blank ...