4–39
System Setup and Setpoints – 4
4.4
System Setpoints
The individual protective functions, along with their
magnitude and timing settings are described in
the following pages. Settings for disabled functions
do not apply. Some menu and setting screens do
not appear for functions that are disabled or not
purchased. Menu screens are as they would appear
on units equipped with the M-3931 HMI Module. The
same setting may be entered using M-3400 IPScom
Communications Software.
The general information required to complete the
input data in this section includes individual relay
function:
• pickup settings (converted to relay
quantities)
• time delay settings
• frequency settings
• time dials
• power level settings (in percent rated)
• impedance diameter in relay ohms for
distance and offset settings
Setpoint Profiles (Setting Groups)
Up to four setpoint profiles may be used. Each
profile contains a function configuration and
associated settings. One of the four profiles may be
designated as the Active Profile which will contain
the parameters that the relay will actively use. Only
the Active Profile may be edited.
The
Active Profile
may be chosen manually or by
contact input. When the profile Switching Method is
set to Manual, the HMI, remote communications or
one of the IPSlogic elements will select the Active
Profile. When the Switching Method is set to Input
Contact, the profile is selected by the input contacts.
When Input Contact is selected, only the input
contacts can switch the relay’s profile, and none of
the Manual methods will switch the profile.
A
Copy Profile
feature is available that copies
an image of the Active Profile to any one of the
other three profiles. This feature can speed up
the configuration process. Consider, for example,
a situation where a breaker will be removed from
service. Two profiles will be used: an “In Service”
profile (Profile 1) and an “Out of Service” profile
(Profile 2).
Profile 2 will be identical to the “In Service” profile,
with the exception of the overcurrent settings. Profile
1 is set to be the Active profile, and all setpoints
entered. An image of Profile 1 will then be copied
to Profile 2 with the Copy Active Profile command.
Profile 2 is then selected as the Active Profile and
the overcurrent setpoints modified.
▲
CAUTION:
During profile switching, relay
operation is disabled for approximately 1 second.
Utilizing the above feature not only accelerates
the configuration process, but also removes the
possibility of errors if all setpoints are re-entered
manually.
Configure Relay Data
The relay is shipped with a certain group of standard
functions, including other optional functions, as
purchased. Both of these groups define a configurable
set of functions. Only members of this set may be
enabled/disabled by the end user. (Optional functions
not purchased cannot be enabled.)
Functions designated as
DISABLED
are inactive
and will not be available for tripping. All menus
associated with inactive functions will be unavailable.
The general information required to complete the
input data on this section includes:
• enable/disable
• output choices (OUT1–OUT8; for units
with expanded I/O, OUT9–OUT23 may
only be set through IPScom
®
)
• input blocking choices (IN1–IN6; for units
with expanded I/O, IN7–IN14 may only
be set through IPScom), plus fuse loss
blocking
Содержание M-3425A
Страница 1: ...Instruction Book M 3425A Generator Protection ...
Страница 38: ...This Page Left Intentionally Blank ...
Страница 39: ...800 3425A SP 10MC2 07 12 2001 Beckwith Electric Co All Rights Reserved Printed in U S A 01 67 04 25 03 ...
Страница 43: ...This Page Left Intentionally Blank ...
Страница 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Страница 73: ...M 3425A Instruction Book 2 10 Path Monitor Primary Metering Status Figure 2 4 Primary Metering Status Screen ...
Страница 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Страница 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Страница 103: ...M 3425A Instruction Book 3 8 Path Monitor Primary Metering and Status Figure 3 9 Primary Metering Status Screen ...
Страница 105: ...M 3425A Instruction Book 3 10 Path Monitor Secondary Metering and Status Figure 3 10 Secondary Metering Status Screen ...
Страница 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Страница 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Страница 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Страница 180: ...4 49 System Setup and Setpoints 4 Table 4 5 Impedance Calculation Figure 4 30 Phase Distance 21 Setpoint Ranges ...
Страница 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Страница 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Страница 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Страница 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Страница 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Страница 219: ...4 88 M 3425A Instruction Book Figure 4 65 Overvoltage Neutral Circuit or Zero Sequence 59N Setpoint Ranges ...
Страница 236: ...4 105 System Setup and Setpoints 4 Figure 4 77 Residual Directional Overcurrent 67N Setpoint Ranges ...
Страница 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Страница 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Страница 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Страница 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Страница 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Страница 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Страница 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Страница 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Страница 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Страница 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Страница 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Страница 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Страница 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Страница 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Страница 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Страница 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Страница 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Страница 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Страница 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Страница 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 481: ...This Page Left Intentionally Blank ...