4–50
M‑3425A Instruction Book
24 Overexcitation Volts/Hz
The Volts-Per-Hertz function (24) provides
overexcitation protection for the generator and unit-
connected transformers. This function incorporates
two definite time elements which can be used to
realize traditional two-step overexcitation protection.
In addition, the relay includes an inverse time
element that provides superior protection by
closely approximating the combined generator/unit
transformer overexcitation curve. Industry standard
inverse time curves may be selected along with
a linear reset rate which may be programmed to
match specific machine cooling characteristics. The
percent pickup is based on the Nominal Voltage
setting and the nominal frequency. The V/Hz function
provides reliable measurements of V/Hz up to 200%
for a frequency range of 2–80 Hz. The ranges and
increments are presented in Figure 4-32.
Setting this relay function involves determining
the desired protection levels and operating times.
The first step is to plot the combined generator
and associated unit transformer overexcitation
capability limits. This data is typically available
from the manufacturer and should be plotted on
the same voltage base. Depending on the resulting
characteristic, one of the four families of inverse
time curves (as shown in Appendix D,
Inverse Time
Curves
) can be matched to provide the protection.
The two definite time elements can be used to
further shape the protection curve or provide an
alarm.
Figure 4-31 illustrates a composite graph of
generator and transformer limits, a chosen inverse
time curve and pickup, and a definite time pickup
and delay.
24DT #1 PICKUP
%
24DT #1 DELAY
Cycles
24DT #2 PICKUP
%
24DT #2 DELAY
Cycles
24IT PICKUP
%
24IT CURVE
crv#1 crv#2 crv#3 crv#4
24IT TIME DIAL
24IT RESET RATE
Seconds
Definite time setpoint #1 establishes the V/Hz level above
which the protection operating time will be fixed at the
definite time delay #1.
Delay time #1 establishes the operation time of the
protection for all V/Hz values above the level set by definite
time setpoint #1.
Definite time setpoint #2 could be programmed to alarm,
alerting the operator to take proper control action to
possibly avoid tripping.
Time to operation at any V/Hz value exceeding Definite
time setting #2.
The pickup value is the V/Hz value at which the chosen
inverse curve begins protective operation. Typical value is
105%.
Allows the user to designate the appropriate curve family
for this protection application. These curves are shown in
Appendix D,
Inverse Time Curves
.
The appropriate curve in the family is designated by the
associated “K” value of the curve.
The value entered here should be the time needed for the
unit to cool to normal operating temperature if the V/Hz
excursion time was just under the trip time.
Содержание M-3425A
Страница 1: ...Instruction Book M 3425A Generator Protection ...
Страница 38: ...This Page Left Intentionally Blank ...
Страница 39: ...800 3425A SP 10MC2 07 12 2001 Beckwith Electric Co All Rights Reserved Printed in U S A 01 67 04 25 03 ...
Страница 43: ...This Page Left Intentionally Blank ...
Страница 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Страница 73: ...M 3425A Instruction Book 2 10 Path Monitor Primary Metering Status Figure 2 4 Primary Metering Status Screen ...
Страница 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Страница 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Страница 103: ...M 3425A Instruction Book 3 8 Path Monitor Primary Metering and Status Figure 3 9 Primary Metering Status Screen ...
Страница 105: ...M 3425A Instruction Book 3 10 Path Monitor Secondary Metering and Status Figure 3 10 Secondary Metering Status Screen ...
Страница 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Страница 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Страница 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Страница 180: ...4 49 System Setup and Setpoints 4 Table 4 5 Impedance Calculation Figure 4 30 Phase Distance 21 Setpoint Ranges ...
Страница 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Страница 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Страница 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Страница 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Страница 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Страница 219: ...4 88 M 3425A Instruction Book Figure 4 65 Overvoltage Neutral Circuit or Zero Sequence 59N Setpoint Ranges ...
Страница 236: ...4 105 System Setup and Setpoints 4 Figure 4 77 Residual Directional Overcurrent 67N Setpoint Ranges ...
Страница 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Страница 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Страница 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Страница 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Страница 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Страница 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Страница 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Страница 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Страница 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Страница 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Страница 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Страница 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Страница 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Страница 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Страница 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Страница 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Страница 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Страница 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Страница 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Страница 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...
Страница 481: ...This Page Left Intentionally Blank ...