M-3425 Instruction Book
6–36
51V Inverse Time Phase Overcurrent with Voltage Control/Restraint
VOLTAGE INPUTS: V1
CURRENT INPUTS: C1
TEST SETTINGS:
Pickup
P
Amps
(0.5 to 12.00)
Inverse Time Curve
C
(1 to 4)
Time Dial
K
(0.5 to 11)
Voltage Control Setting
V
Volts
(5 to 180)
Programmed Outputs
Z
OUT
(1 to 8)
Functions 21, 27, 27TN
Disable
Functions 32, 40, 46
Disable
Functions 50, 50/27, 51T
Disable
Functions 87, 87GD
Disable
1.
Disable functions as shown. See Section 3.2, Initial Setup Procedure/Settings, Configure Relay
Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect voltage input in Configuration V1 designated above. See Section 6.1, Equipment/Test
Setup for configurations.
4.
Test levels may be chosen at any ampere values which are a minimum of 50% higher than the
pickup amps, P Amps. It is suggested that the user select 4 or 5 test levels to verify curve.
5.
For VC or Voltage Controlled Units: Set the input voltages at least 5% under the Voltage
Control setting V.
6.
Time Test: With output contacts (Z) connected to stop the timer, input current equal to the
chosen test level calculated in step 4 on A phase and start timing. The operating time will be as
read from the appropriate Inverse Curve Family and K (Time Dial) setting in Appendix D, Figures
D-5 through D-8, or Tables D-1A through D-1B. Repeat this step for all test levels chosen. The
accuracy specified is valid for currents above 1.5 times the pickup current.
7.
Voltage Control Test: The input voltage may be increased over the Voltage Control setting by at
least 0.5 Volts and the function will dropout.
8.
For VR or Voltage Restrained Units: Input Nominal Voltages and test as in steps 4, 5, and 6
above (same current input values). Repeat steps 4, 5, and 6 with reduced input voltage values
and current reduced by the same percentage as value (see Figure 2-14).
9.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this
configuration.
Содержание M-3425
Страница 1: ...Instruction Book M 3425 Generator Protection ...
Страница 14: ... 13 M 3425 Generator Protection Relay Figure 1 External Connections ...
Страница 33: ...x M 3425 Instruction Book This Page Left Intentionally Blank ...
Страница 89: ...M 3425 Instruction Book 2 52 This Page Left Intentionally Blank ...
Страница 125: ...1 3 A B C M 3425 Instruction Book 4 26 This Page Left Intentionally Blank ...
Страница 187: ...M 3425 Instruction Book 6 50 This Page Left Intentionally Blank ...
Страница 207: ...M 3425 Instruction Book C 4 This Page Left Intentionally Blank ...
Страница 209: ...D 2 M 3425 Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Страница 210: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Страница 211: ...D 4 M 3425 Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Страница 212: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Страница 215: ...D 8 M 3425 Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Страница 216: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Страница 217: ...D 10 M 3425 Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Страница 218: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Страница 223: ...D 16 M 3425 Instruction Book This Page Intentionally Left Blank ...