M-3425 Instruction Book
6–26
VOLTAGE INPUTS:Configuration V1
CURRENT INPUTS: Configuration C1 (MODIFIED)
TEST SETTINGS:
Pickup Def Time
P
%
(3 to 100)
Time Delay
D
cycles
(1 to 8160)
Programmed Outputs
Z
OUT
(1 to 8)
Function 27TN, 32, 50
Disable
Functions 51T, 51V, 87
Disable
Function 46 Inv Time
Disable
■
■
■
■
■
NOTE: Although no voltage input is required for the testing of the 46 function, it is suggested that
Nominal Volts be applied to restrain the functions which use both voltage and current inputs for
operation. If other functions operate during these tests they should also be disabled for the test and
enabled after the tests are complete.
1.
Disable functions as shown. See Section 3.2, Initial Setup Procedure/Settings, Configure Relay
Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 and C1 (MODIFIED) designated above. The modification to C1
(See Section 6.1, Equipment/Test Setup for configuration) is to exchange Current input 2 and 3
(phase B current = input 3 and phase C current = input 2). Set Voltages = Nominal voltage.
4.
The level of current at which operation is to be expected for an individual setting is: Pickup current
= (P% ÷ 100) x (Nominal Current) where the Nominal Values have been programmed in the
system setup data described in Section 2.1, Configuration and should be recorded on Figure A-2,
Communication Data and Unit Setup Record Form.
5.
Pickup Test: Press and hold the TARGET RESET button and slowly increase the three-phase
currents until the appropriate NEG SEQ OVERCURRENT 46 LED light goes on or the pickup
indicator operates on the computer target screen. The level will be equal to pickup current
calculated in step 4 ±0.5% of 5 A.
6.
Release TARGET RESET button and decrease the currents and OUTPUT LEDs will go out. Press
TARGET RESET button to remove targets.
7.
Time Test: With output contacts (Z) connected to stop the timer, apply current of at least (1.1 x
pickup) amps and start timing. The contacts will close after D cycles within
"
1 cycle or
"
1%.
8.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this
configuration.
(For proper testing, use I
≤
3 x CT rating)
46 Negative Sequence Overcurrent Definite Time
Содержание M-3425
Страница 1: ...Instruction Book M 3425 Generator Protection ...
Страница 14: ... 13 M 3425 Generator Protection Relay Figure 1 External Connections ...
Страница 33: ...x M 3425 Instruction Book This Page Left Intentionally Blank ...
Страница 89: ...M 3425 Instruction Book 2 52 This Page Left Intentionally Blank ...
Страница 125: ...1 3 A B C M 3425 Instruction Book 4 26 This Page Left Intentionally Blank ...
Страница 187: ...M 3425 Instruction Book 6 50 This Page Left Intentionally Blank ...
Страница 207: ...M 3425 Instruction Book C 4 This Page Left Intentionally Blank ...
Страница 209: ...D 2 M 3425 Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Страница 210: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Страница 211: ...D 4 M 3425 Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Страница 212: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Страница 215: ...D 8 M 3425 Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Страница 216: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Страница 217: ...D 10 M 3425 Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Страница 218: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Страница 223: ...D 16 M 3425 Instruction Book This Page Intentionally Left Blank ...