6–19
Testing – 6
24 Volts/Hz Definite Time (#1 or #2)
VOLTAGE INPUTS: V1
CURRENT INPUTS: none
TEST SETTINGS:
Definite Time Pickup
P
%
(100 to 200)
Time Delay
D
cycles
(30 to 8160)
Programmed Outputs
Z
OUT
(1 to 8)
Functions 24IT, 27, 27TN
Disable
Function 24 DT (#1 or #2)
Disable
Functions 32, 59, 81, 81R
Disable
■
■
■
■
■
NOTE: It would be efficient to disable the 24 Definite Time function with the lower pickup setting
first and test the higher setting operation. Since the lower setting operation can be tested without
disabling the higher setting, the 24 Definite Time functions will be enabled when the tests are complete.
1.
Disable functions as shown. See Section 3.2, Initial Setup Procedure/Settings, Configure Relay
Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect input in Configuration V1 as designated above. See Section 6.1, Equipment/Test Setup
for configurations.
4.
The Volts per Hertz pickup level at a percentage setting at nominal frequency (50 or 60 Hz) is:
Pickup voltage = (P% ÷ 100) x (Nominal Voltage) where the Nominal Values have been
programmed in the system setup data described in Section 2.1, Configuration and are recorded on
the COMMUNICATION & UNIT SETUP RECORD FORM.
5.
Pickup Test: Hold the TARGET RESET button in and slowly increase the voltage on A phase
until the 24 VOLTS/HZ LED light goes on or the pickup indicator operates on the computer target
screen. The voltage level of operation will equal P volts ±1%. Release the TARGET RESET
button and decrease the voltage and the output LEDs will go out. Press TARGET RESET button
to remove targets.
6.
Time Test: With output contacts (Z) connected to stop the timer, apply approximately (P + 10
volts) volts and start timing. The contacts will close after D cycles within 25 cycles.
7.
Test phases B and C by repeating steps 4 and 5.
8.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this
configuration.
Содержание M-3425
Страница 1: ...Instruction Book M 3425 Generator Protection ...
Страница 14: ... 13 M 3425 Generator Protection Relay Figure 1 External Connections ...
Страница 33: ...x M 3425 Instruction Book This Page Left Intentionally Blank ...
Страница 89: ...M 3425 Instruction Book 2 52 This Page Left Intentionally Blank ...
Страница 125: ...1 3 A B C M 3425 Instruction Book 4 26 This Page Left Intentionally Blank ...
Страница 187: ...M 3425 Instruction Book 6 50 This Page Left Intentionally Blank ...
Страница 207: ...M 3425 Instruction Book C 4 This Page Left Intentionally Blank ...
Страница 209: ...D 2 M 3425 Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Страница 210: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Страница 211: ...D 4 M 3425 Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Страница 212: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Страница 215: ...D 8 M 3425 Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Страница 216: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Страница 217: ...D 10 M 3425 Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Страница 218: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Страница 223: ...D 16 M 3425 Instruction Book This Page Intentionally Left Blank ...