Version: 1.8.0
Channel Interface
Description
Both Deactivated
Both inputs are deactivated
Single-Channel 1 Activated
Channel 1: Single-channel evaluation
Channel 2: deactivated
Single-Channel 2 Activated
Channel 1: deactivated
Channel 2: Single-channel evaluation
Single-Channel Both Activated
Channel 1: Single-channel evaluation
Channel 2: Single-channel evaluation
Two-Channel
Both inputs are activated, and two-channel evaluation with
Discrepancy Time (ms)
If the
Two-Channel
evaluation is enabled, the corresponding
Discrepancy time (ms)
can be set in
milliseconds. For each input there is a setting to indicate whether the input should be evaluated as
Break
Contact (NC)
or
Make Contact (NO)
. When a variable or a connecting line is connected to the function block,
the corresponding channel is enabled automatically.
Fig. 56: Make Contact (NO) / Break Contact (NC) setting
These settings are also accessible for each individual port of an FB via the context menu item
Change InPort
Settings
.
Содержание TwinSAFE EL6910
Страница 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Страница 2: ......
Страница 62: ...Operation EL6910 62 Version 1 8 0 Fig 63 Check Safe Addresses context menu Fig 64 Check Safe Addresses dialog...
Страница 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Страница 71: ...Operation EL6910 71 Version 1 8 0 Fig 75 Group Status Online ERROR Fig 76 Group Status Online STOP...
Страница 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Страница 137: ...Appendix EL6910 137 Version 1 8 0...