Operation
EL6910
125
Version: 1.8.0
Logic error codes of LED Diag 2 (if LED Diag 1 is lit)
Flashing
Code
Description
1
Function block error in one of the TwinSAFE groups
2
Communication error in one of the TwinSAFE groups
3
Error combination: Function block and communication
4
General error in one of the TwinSAFE groups
5
Error combination: General and function block
6
Error combination: General and communication
7
Error combination: General, function block and communication
Environment error codes of LED Diag 2 (if LED Diag 1 is off)
Flashing
Code
Description
1
Maximum supply voltage µC1 exceeded
2
Supply voltage µC1 below minimum value
3
Maximum supply voltage µC2 exceeded
4
Supply voltage µC2 below minimum value
5
Maximum internal temperature exceeded
6
Internal temperature below minimum value
7
Valid temperature difference between µC1 and µC2 exceeded
8
not used
9
not used
10
General error
4.18.1.2
Flash code display
LED
Display
Description
flashing
400 ms ON / 400 ms OFF
1 second pause between the flash codes
flickering
50 ms ON / 50 ms OFF
4.18.2
Status LEDs
The LEDs State 1 to State 4 indicate the current status of the EL6910.
Fig. 177: EL6910 status LEDs
Содержание TwinSAFE EL6910
Страница 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Страница 2: ......
Страница 62: ...Operation EL6910 62 Version 1 8 0 Fig 63 Check Safe Addresses context menu Fig 64 Check Safe Addresses dialog...
Страница 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Страница 71: ...Operation EL6910 71 Version 1 8 0 Fig 75 Group Status Online ERROR Fig 76 Group Status Online STOP...
Страница 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Страница 137: ...Appendix EL6910 137 Version 1 8 0...