Operation
EL6910
121
Version: 1.8.0
4.16
Project design limits of EL6910/EJ6910
Project design limits
The maximum project design size for EL6910/EJ6910 is determined by the available memory. This
is managed dynamically. The values specified in the following table are therefore only guide values
and may differ from the actual values, depending on the safety project.
Process image size
max. 1486 bytes per data direction
(max. memory size 0x1E00 for three buffers, i.e. with identical input and
output process data sizes, the maximum size is 1280 bytes per data
direction. Only even start addresses are possible, therefore fill bytes may
have to be considered)
TwinSAFE connections
maximum 212
(up to 255 CRCs in total; 1 CRC is required for a TwinSAFE connection
with 1 or 2 byte safe data.)
Supported hardware for
TwinSAFE connections of the
EL6910/EJ6910
EL1904 (all)
EL2904 (all)
EL2902 (all)
EL6900 (all - max. 14 byte safe data)
EL6930 (all - max. 14 byte safe data)
EL6910 (all - max. 126 byte safe data)
EL6910 (all - max. 126 byte safe data)
KL1904 (from 2008)
KL2904 (from 2008)
KL6904 as slave (from 2008)
AX5805 (all)
AX5806 (all)
Safe data per TwinSAFE
connection
maximum 126 byte (telegram length 255 byte)
PROFIsafe telegram length
4 to 16 byte PROFIsafe telegram length (user data 0 - 12 byte)
TwinSAFE function blocks
maximum 512 (ESTOP with complete input and output mapping)
TwinSAFE groups
maximum 128
TwinSAFE user
maximum 40
Standard PLC inputs
dynamic (memory-dependent), max. 1024 byte
Standard PLC outputs
dynamic (memory-dependent), max. 1024 byte
TwinSAFE connection
Only one TwinSAFE connection between two TwinSAFE terminals is possible. For communication
with a EL6900, for sample, a connection with up to 14 bytes safe user data can be used.
4.17
Sync-Manager Configuration
Depending on the size of the TwinSAFE project on the TwinSAFE logic, it may be necessary to adjust the
sync manager configuration.
As soon as the following message appears during the saving or downloading of the project, the sync
manager configuration for the device has to be adapted.
Содержание TwinSAFE EL6910
Страница 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Страница 2: ......
Страница 62: ...Operation EL6910 62 Version 1 8 0 Fig 63 Check Safe Addresses context menu Fig 64 Check Safe Addresses dialog...
Страница 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Страница 71: ...Operation EL6910 71 Version 1 8 0 Fig 75 Group Status Online ERROR Fig 76 Group Status Online STOP...
Страница 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Страница 137: ...Appendix EL6910 137 Version 1 8 0...