Operation
EL6910
104
Version: 1.8.0
Fig. 140: Creating a Custom PROFIsafe connection
After opening the alias device, the process image size of the connection can be set via the
Process Image
tab. The individual signals can be renamed, so that this text is displayed within the logic.
Fig. 141: Process image
Set the safe address on the
Linking
tab. Under Full Name (input) and Full Name (output) it contains
information on which process data have to be linked with the corresponding signals of the PROFIsafe
control. The entry
Safe Address
must be used as F_Dest_Add on the master side.