Fault correction
104
───
Version: 2.2
XTS
12.2
TcIoXts object
12.2.1
Warning
12.2.1
ID
Message
Cause
Number of the solution
5000
The XTS is designed to run
with a cycle time of 250 us.
Other cycle times are not sup-
ported
Cycle time of the XTS task is not
equal to 250 µs:
A cycle time of 375 µs is also possi-
ble, but leads to losses of perfor-
mance
1
5001
Too few movers are detected.
Expected = "x", Detected =
"y"
Fewer movers on the XTS than con-
figured in the TcIoXtsDrv object
EtherCAT Distributed Clocks settings
incorrect
Use of wrong teaching data
2
4
5002
Too many movers are de-
tected. Expected = "x", De-
tected = "y"
More movers on the XTS than config-
ured in the TcIoXtsDrv object
EtherCAT Distributed Clocks settings
incorrect
Use of wrong teaching data
2
4
5003
Teaching file "Bezeich-
nungsstring" ("Designation
string") is missing
Teaching file "Designation string"
missing
3
4
5004
Teaching file of XTS module
"x" is invalid
Damaged or missing teaching file in
the folder:
"C:\TwinCAT\3.1\Target\Config
\TcIoXts"
4
5005
Abnormal behavior is de-
tected. All values of XTS
module "x" are zero
All values in the teaching file are 0
Teaching file is probably corrupt
4
5006
Abnormal behavior is de-
tected. All values of XTS
module "x" are negative.
All values on the sensor side of the
XTS motor module are negative
5
5007
Abnormal behavior is de-
tected. All values of XTS
module "x" are positive.
All values are positive on the sensor
side of the XTS motor module
5
5008
Abnormal behavior is de-
tected. Some values of XTS
module "x" are not in the ex-
pected range (-400, 400)
Offset values too high with some sen-
sors of the XTS motor module
6
5009
Is waiting for EtherCAT de-
vice "x" to start up.
EtherCAT Master Device "x" not
ready to operate, or no connection to
the slaves
7
5010
Mover "x" is frozen at position
"y"
EtherCAT connection interrupted, po-
sition "y" is at the transition from a
motor module to a power supply mod-
ule
Incorrectly order of power supply
modules when configuring the XTS
8
5011
The Mover1 Detection has al-
ready been started. Do not
start it again.
Mover 1 detection already carried out
or restarted during running search:
The Mover 1 detection requires a cer-
tain time, depending on the number of
movers
9
5012
Wait for Mover Detection be-
fore starting MoverIdDetec-
tion
MoverID detection started before
completion of the standard mover de-
tection
10
5013
The system is waiting for trig-
gering the MoverIdDetection
(via PLC or manually)
Mover 1 function configured in the pa-
rameters (Init), but no mover 1 found
11
Содержание eXtended Transport System
Страница 1: ...XTS eXtended Trans port System Operating Instructions EN 4 20 2020 Version 2 2 ...
Страница 2: ......
Страница 30: ...Product overview 30 Version 2 2 XTS 3 6 3O shape 3 6 3 3 6 4Z shape 3 6 4 ...
Страница 39: ...Technical data Version 2 2 39 XTS AT2000 0233 Motor straight 233 mm All figures in millimeters ...
Страница 40: ...Technical data 40 Version 2 2 XTS AT2002 0249 Motor straight 249 mm with plug All figures in millimeters ...
Страница 41: ...Technical data Version 2 2 41 XTS AT2002 0250 Motor straight 250 mm with plug All figures in millimeters ...
Страница 45: ...Technical data Version 2 2 45 XTS AT2026 0250 Motor 22 5 curved with power supply All figures in millimeters ...