Overview CoE objects EL6002, EL6022
EL600x, EL602x
185
Version: 4.6
Control data
Bit position Name
Meaning
Data type
0
Transmit request By changing the state of this bit, the controller informs the
terminal that the DataOut bytes contain the number of bytes
displayed in “Output length”. The terminal acknowledges
receipt of the data by changing the state of the
“TransmitAccepted” bit. Only now new data can be transferred
from the controller to the terminal.
BOOLEAN
1
Receive accepted The controller acknowledges receipt of data by changing the
state of this bit. Only then new data can be transferred from
the terminal to the controller.
BOOLEAN
2
Init request
0 The controller once again requests the terminal to prepare
for serial data exchange.
BOOLEAN
1 The controller requests terminal for initialization. The
transmit and receive functions will be blocked, the FIFO
pointer will be reset and the interface will be initialized with
the values of the responsible Settings object. The execution
of the initialization will be acknowledged by the terminal
with the ‘Init accepted’ bit.
3
Send continuous Continuous sending of data from the FIFO.
The send buffer is filled (up to 128 bytes) by the controller. The
filled buffer contents will be sent on the rising edge of the bit. If
the data has been transmitted, the terminal informs the
controller by setting the “Init accepted” bit. “Init accepted” is
cleared with “SendContinuous”.
BOOLEAN
4...7
-
8...15
Output length
Number of output bytes available for transfer from the
controller to the terminal.
UINT8
PDO Assignment
The terminal makes two input/output process images available for each channel. These differ only in the
representation of the control/status data.
In the case of bitwise representation, the data is made available as shown in the tables above. In the case of
word-wise representation, the first 16 bits of the process data are combined in one word.
The process data objects begin as standard with a control/status word. This PDO assignment is required in
order to use the ‘TwinCAT PLC Serial Communication’ library.
Status Inputs
Control Outputs
Representation
0x1A00
0x1600
bitwise Ch. 1
0x1A01
0x1601
bitwise Ch. 2
0x1A02
0x1602
bitwise Ch. 3
0x1A03
0x1603
bitwise Ch. 4
0x1A04
0x1604
word-wise Ch 1
0x1A05
0x1605
word-wise Ch 2
0x1A06
0x1606
word-wise Ch 3
0x1A07
0x1607
word-wise Ch 4