Overview of CoE objects EL6001, EL6021
EL600x, EL602x
163
Version: 4.6
Index 0x6001 COM ext. inputs
Index
(hex)
Name
Meaning
Data type
Flags
Default
6001:0
COM ext. inputs
UINT8
RO
0x00 (0
dec
)
6001:01
Transmit accepted
identical to index 0x6000
BOOLEAN
RO
0x00 (0
dec
)
6001:02
Receive request
BOOLEAN
RO
0x00 (0
dec
)
6001:03
Init accepted
BOOLEAN
RO
0x00 (0
dec
)
6001:04
Buffer full
BOOLEAN
RO
0x00 (0
dec
)
6001:05
Parity error
BOOLEAN
RO
0x00 (0
dec
)
6001:06
Framing error
BOOLEAN
RO
0x00 (0
dec
)
6001:07
Overrun error
BOOLEAN
RO
0x00 (0
dec
)
6001:09
Input length
UINT8
RO
0x00 (0
dec
)
6001:11
Data In 0
UINT16
RO
0x0000 (0
dec
)
....
6001:42
Data In 49
UINT16
RO
0x0000 (0
dec
)
Index 0x7000 COM Outputs
Index
(hex)
Name
Meaning
Data type
Flags
Default
7000:0
COM Outputs
Max. SubIndex (hex)
UINT8
RO
0x26 (38
dec
)
7000:01
Transmit request
By changing the state of this bit, the controller informs
the terminal that the DataOut bytes contain the number
of bytes displayed in “
”. The ter-
minal acknowledges receipt of the data by changing
the state of the “
” bit. Only
now new data can be transferred from the controller to
the terminal.
BOOLEAN
RO
0x00 (0
dec
)
7000:02
Receive accepted
The controller acknowledges receipt of data by chang-
ing the state of this bit. Only then new data can be
transferred from the terminal to the controller.
BOOLEAN
RO
0x00 (0
dec
)
7000:03
Init request
0
The controller once again requests the terminal to
prepare for serial data exchange.
BOOLEAN
RO
0x00 (0
dec
)
1
The controller requests terminal for initialization.
The transmit and receive functions will be blocked,
the FIFO pointer will be reset and the interface will
be initialized with the values of the responsible Set-
tings object. The execution of the initialization will
be acknowledged by the terminal with the ‘
’ bit.
7000:04
Send continuous
Continuous sending of data from the FIFO.
The send buffer is filled (up to 128 bytes) by the con-
troller. The filled buffer contents will be sent on the ris-
ing edge of the bit. If the data has been transmitted, the
terminal informs the controller by setting the “
”.
BOOLEAN
RO
0x00 (0
dec
)
7000:09
Output length
Number of output bytes available for transfer from the
controller to the terminal.
UINT8
RO
0x00 (0
dec
)
7000:11
Data Out 0
Output byte 0
UINT8
RO
0x00 (0
dec
)
...
...
....
...
...
...
7000:26
Data Out 21
Output byte 21
UINT8
RO