Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
77
Version: 1.2
Fig. 80: typ. attenuation curve notch.filter at 50 Hz
Filter data FIR filter (1- to 4-channel modules)
Filter
Attenuation
Limit frequency (-3 dB)
Conversion time
50 Hz FIR
> 50 dB
22 Hz
625 µs
60 Hz FIR
> 45 dB
26 Hz
521 µs
•
IIR filter
The filter with IIR characteristics is a discrete time, linear, time invariant filter that can be set to eight
levels (level 1 = weak recursive filter, up to level 8 = strong recursive filter).
The IIR can be understood to be a moving average value calculation after a low-pass filter.
Filter characteristics for IIR filters
IIR filter
~3 dB limit frequency at 500 µs sampling time
IIR 1
400 Hz
IIR 2
220 Hz
IIR 3
100 Hz
IIR 4
50 Hz
IIR 5
24 Hz
IIR 6
12 Hz
IIR 7
6.2 Hz
IIR 8
3.0 Hz