![Beckhoff EPI3 Series Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/beckhoff/epi3-series/epi3-series_documentation_2719368036.webp)
Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
36
Version: 1.2
Fig. 35: online display example
Please note:
• all slaves should be in OP state
• the EtherCAT master should be in “Actual State” OP
• “frames/sec” should match the cycle time taking into account the sent number of frames
• no excessive “LostFrames” or CRC errors should occur
The configuration is now complete. It can be modified as described under the offline procedure.
The connected IO-Link master (EP6224-2022) is displayed in the TwinCAT structure as you can see in the
figure below.
Fig. 36: Master display after scan for boxes
Troubleshooting
Various effects may occur during scanning.
• An
unknown device
is detected, i.e. an EtherCAT slave for which no ESI XML description is available.
In this case the System Manager offers to read any ESI that maybe stored in the device.