Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
63
Version: 1.2
Fig. 67: Settings of the IO-Link devices
1.
Information
This field is for information only; the IODD that was read in is displayed under Device Description. Fur-
thermore, the VendorID, DeviceID and the IO-Link revision(V 1.0 or V 1.1) of the IO-Link devices are
displayed. If the device is an IO-Link device V1.1, then the
function is sup-
ported.
The following settings can be made in the settings for the IO-Link devices (see figure above):
2.
Start-up checks
This parameter can be used to specify that the Vendor ID and Device ID should be checked when the
IO-Link device starts up. This avoids errors when exchanging IO-Link devices.
3.
CycleTime
Specifies the cycle time for the IO-Link master
4.
Communication mode
Selection of the mode in which the IO-Link port is to be operated.
◦
Communication
: Default mode for IO-Link devices
◦
StdDigIn
/
StdDigOut
: Mode for non-IO-Link devices, automatically selected if the port is
configured as a
5.
Error Reaction
◦ If the
Set Input Data to 0
field is activated
-> input data are set to 0 in case of error
-> Status display:
Error
6.
Button "Advanced"