Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
50
Version: 1.2
Fig. 51: AoE-NetID allocation
PortNo
The individual IO-Link ports for the master are allocated via the port number. The port numbers are allocated
in ascending order from 0x1000. I.e. IO-Link Port1 === PortNo 0x1000 and IO-Link Portn === PortNo
n-1.
The following specification applies for the EP6224 (4-port IO-Link master):
IO-Link Port1 === PortNo 0x1000
IO-Link Port2 === PortNo 0x1001
IO-Link Port3 === PortNo 0x1002
IO-Link Port4 === PortNo 0x1003
ADS Indexgroup
As for CoE, the Indexgroup of an ADS command is specified as 0xF302 for the IO link data channel.
ADS Indexoffset
The IO link addressing with index and subindex is coded in the Indexoffset. The Indexoffset has a size of 4
bytes and is subdivided as follows: 2-byte index, 1-byte reserve, 1-byte subindex.
• Example: Indexoffset 0x12340056 corresponds to index 0x1234 and subindex 56
Example with ADS monitor
Reading of the Application-Specific Name, index 0x0018 subindex 0x00 (see figure below).