Commissioning and Configuration
EP8309-1022
62
Version: 2.0.0
The following entries are available:
Value
Text
Description
0
Actual current
Actual current in mA
1
Set current
Set current in mA
2
Duty Cycle
The PWM duty cycle of the output stage. A value of 1000 corresponds to
100% duty cycle.
Watchdog
The analog output value can, e.g. in the case of a failure of communication with the controller, be set to a
user-specific value.
Fig. 58: Watchdog
Three parameterization options are available for this purpose:
Behavior
0: Default watchdog value
The substitute switching value (
) is output on error.
1: Watchdog ramp active
On error the output value is moved to the default value (
) with the ramp time set under
The ramp time is specified in digits / ms.
If the entry is 100 and the default value 0, for example, it takes
327 ms (32767/100) for the output value to change from the
maximum value (32767) to the default value in the event of a fault.
2: Last output value active
In the event of a fault (watchdog drop) the last process data is
issued.