Commissioning and Configuration
EP8309-1022
60
Version: 2.0.0
Fig. 55: Switching the PWMi/analog output - analog mode
5.5
Quick start
Parameterization of the main settings
The module is factory-set such that in most applications it is operational without further parameterization.
Set the parameter
Max Current [%]
(
) such that the maximum inductance current is not
exceeded. If an EP8309 with 1.2 A rated current and an inductance with a maximum current of 600 mA is
used, this parameter can be set to 50 (50%). This means that, at a maximum process data value of 32767
dec
a coil current of +600 mA is reached (not +1 A).
Info data objects
Via the info data objects additional information can be transferred synchronously. For each channel two of
these objects are available.
The synchronous info data can be activated in the TwinCAT System Manager via the "Process Data" tab
(0x1A07).