Commissioning and Configuration
EP8309-1022
84
Version: 2.0.0
Index 8070 AO Settings
Index (hex) Name
Meaning
Data type
Flags
Default
8070:0
AO Settings
UINT8
RO
0x16 (22
dec
)
8070:01
Enable user scale
This entry activates the scaling for 0x8pp0:11 and
0x8pp0:12.
BOOLEAN
RW
0x00 (0
dec
)
8070:02
Presentation
0: Signed presentation
The output value range 0x7pp1:11 is shown as 16 bit
signed integer. For unipolar terminals (0-10V or 0-20 mA)
the negative range is set to zero.
1: Unsigned presentation The output value range
0x7pp1:11 is shown as 16 bit unsigned integer. Negative
values are not possible.
2: Absolute value with MSB as sign, signed amount rep-
resentation is active.
3: Absolute value, the absolute value of the signed repre-
sentation is formed.
BIT3
RW
0x00 (0
dec
)
8070:05
Watchdog
0: Default watchdog value
The default value (0x8pp0:13) is active.
1: Watchdog ramp
The ramp (0x8pp0:14) for moving to the default value
((0x8pp0:13)) is active.
2: Last output value
In the event of a fault (watchdog drop) the last process
data is issued.
BIT2
RW
0x00 (0
dec
)
8070:07
Enable user calibra-
tion
Enabling of the user calibration
BOOLEAN
RW
0x00 (0
dec
)
8070:08
Enable vendor cali-
bration
Enable vendor calibration
BOOLEAN
RW
0x01 (1
dec
)
8070:11
User scale offset
This is the user scaling offset
INT16
RW
0x0000 (0
dec
)
8070:12
User scale gain
This is the user scaling gain. The gain is a fixed-point
number with the factor 2^-16. The value 1 corresponds to
65535 (0x00010000).
INT32
RW
0x00010000
(65536
dec
)
8070:13
Default output
This is the default output value
INT16
RW
0x0000 (0
dec
)
8070:14
Default output ramp
This value defines the ramps for the ramp-down to the
default value. The value is specified in digits / ms.
If the entry is 100 and the default value 0, for example, it
takes 327 ms (32767/100) for the output value to change
from the maximum value (32767) to the default value in
the event of a fault.
UINT16
RW
0xFFFF
(65535
dec
)
8070:15
User calibration offset User calibration offset
INT16
RW
0x0000 (0
dec
)
8070:16
User calibration gain
User gain compensation
UINT16
RW
0x4000
(16384
dec
)
Index F800 AIAO Range settings
Index (hex) Name
Meaning
Data type
Flags
Default
F800:0
AIAO Range settings
UINT8
RO
0x08 (8
dec
)
F800:01
Input type Ch1
Select input type for Ch1
UINT16
RW
0x0001 (1
dec
)
F800:02
Input type Ch2
Select input type for Ch2
UINT16
RW
0x0001 (1
dec
)
F800:08
Output type
Select input type for Ch1
UINT16
RW
0x0001 (1
dec
)
5.7.3.2
Objects for regular operation
The EP8309 has no such objects.
Содержание EP8309-1022
Страница 1: ...Documentation for EP8309 1022 Multi functional I O Box 2 0 0 2017 11 07 Version Date...
Страница 2: ......