Commissioning and Configuration
EP8309-1022
92
Version: 2.0.0
Index 1C32 SM output parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C32:0
SM output parameter Synchronization parameters for the outputs
UINT8
RO
0x20 (32
dec
)
1C32:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchronous with SM 2 event
• 2: DC-Mode - Synchronous with SYNC0 Event
• 3: DC-Mode - Synchronous with SYNC1 event
UINT16
RW
0x0001 (1
dec
)
1C32:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchronous with SM 2 event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x000F4240
(1000000
dec
)
1C32:03
Shift time
Time between SYNC0 event and output of the outputs (in
ns, DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:04
Sync modes sup-
ported
Supported synchronization modes:
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchronous with SM 2 event is
supported
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 10: Output shift with SYNC1 event (only
DC mode)
• Bit 14 = 1: dynamic times (measurement through
UINT16
RO
0xC007
(49159
dec
)
1C32:05
Minimum cycle time
Minimum cycle time (in ns)
UINT32
RO
0x0007A120
(500000
dec
)
1C32:06
Calc and copy time
Minimum time between SYNC0 and SYNC1 event (in ns,
DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:07
Minimum delay time
UINT32
RO
0x00000000
(0
dec
)
1C32:08
Command
• 0: Measurement of the local cycle time is stopped
• 1: Measurement of the local cycle time is started
The entries
,
,
,
,
are updated with
the maximum measured values.
For a subsequent measurement the measured values
are reset
UINT16
RW
0x0000 (0
dec
)
1C32:09
Maximum delay time
Time between SYNC1 event and output of the outputs (in
ns, DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or the
next cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C32:0D
Shift too short counter Number of occasions that the interval between SYNC0
and SYNC1 event was too short (DC mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:20
Sync error
The synchronization was not correct in the last cycle
(outputs were output too late; DC mode only)
BOOLEAN
RO
0x00 (0
dec
)
Содержание EP8309-1022
Страница 1: ...Documentation for EP8309 1022 Multi functional I O Box 2 0 0 2017 11 07 Version Date...
Страница 2: ......