Commissioning and Configuration
EP8309-1022
80
Version: 2.0.0
5.7.3.1
Objects to be parameterized during commissioning
Index 8000 AI Settings Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
8000:0
AI Settings
Maximum subindex
UINT8
RO
0x18 (24
dec
)
8000:01
Enable user scale
1
User scale is active.
BOOLEAN
RW
0x00 (0
dec
)
8000:02
Presentation
0
Signed presentation
BIT3
RW
0x00 (0
dec
)
1
Unsigned presentation
2
Absolute value with MSB as sign (signed amount
representation)
8000:06
Enable filter
1
Enable filter, which makes PLC-cycle-synchro-
nous data exchange unnecessary
BOOLEAN
RW
0x00 (0
dec
)
8000:07
Enable limit 1
1
Limit 1 enabled
BOOLEAN
RW
0x00 (0
dec
)
8000:08
Enable limit 2
1
Limit 2 enabled
BOOLEAN
RW
0x00 (0
dec
)
8000:0A
Enable user calibra-
tion
1
Enabling of the user calibration
BOOLEAN
RW
0x00 (0
dec
)
8000:0B
Enable vendor cali-
bration
1
Enabling of the vendor calibration
BOOLEAN
RW
0x01 (1
dec
)
8000:11
User scale offset
User scale offset
INT16
RW
0x0000 (0
dec
)
8000:12
User scale gain
User scale gain.
The gain is represented in fixed-point format, with the
factor 2
-16
.
The value 1 corresponds to 65535
dez
(0x00010000
hex
)
and is limited to +/- 0x7FFFF
INT32
RW
0x00010000
(65536
dec
)
8000:13
Limit 1
First limit value for setting the status bits
INT16
RW
0x0000 (0
dec
)
8000:14
Limit 2
Second limit value for setting the status bits
INT16
RW
0x0000 (0
dec
)
8000:15
Filter settings
This object determines the digital filter settings
for all
channels of the module
, if it is activated via Enable filter
(index
). The possible settings are se-
quentially numbered.
UINT16
RW
0x0000 (0
dec
)
0
50 Hz FIR
1
60 Hz FIR
2
IIR 1
3
IIR 2
4
IIR 3
5
IIR 4
6
IIR 5
7
IIR 6
8
IIR 7
9
IIR 8
8000:17
User calibration offset User calibration: Offset
INT16
RW
0x0000 (0
dec
)
8000:18
User calibration gain
User calibration: Gain
INT16
RW
0x4000
(16384
dec
)