Commissioning
EL34xx
248
Version: 1.5
6.7.5
EL3483-00xx
6.7.5.1
Restore object
Index 1011 Restore default parameters
Index
(hex)
Name
Meaning
Data type
Flags Default
1011:0
Restore default parameters
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to "
0x64616F6C"
in the set value dia-
log, all backup objects are reset to their delivery state.
UINT32
RW
0x00000000 (0
dec
)
6.7.5.2
Configuration data
Index 80n0 PMX settings (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
Meaning
Data type
Flags
Default
80n0:0
PMX Settings
Max. subindex
UINT8
RO
0x13 (19
dec
)
80n0:11
Voltage Transformer
Ratio
If a voltage transformer is used, its transmission ratio
can be entered here.
REAL32
RW
0x3F800000
(1065353216
dec
)
Index 80n1 PMX Guard Settings (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
Meaning
Data type
Flags
Default
80n1:0
PMX Guard Settings
Max. subindex
UINT8
RO
0x14 (20dec)
80n1:11
Voltage Guard Min
Error
Lower limit value for a voltage error message
REAL32
RW
0x40000000
(1073741824dec)
80n1:12
Voltage Guard Min
Warning
Lower limit value for a voltage warning message
REAL32
RW
0x434F0000
(1129250816dec)
80n1:13
Voltage Guard Max
Warning
Upper limit value for a voltage warning message
REAL32
RW
0x437D0000
(1132265472dec)
80n1:14
Voltage Guard Max
Error
Upper limit value for a voltage error message
REAL32
RW
0x438B0000
(1133182976dec)
Index F800 PMX Settings
Index (hex) Name
Meaning
Data type
Flags
Default
F800:0
PMX Settings
Max. subindex
UINT8
RO
0x15 (21
dec
)
F800:01
Reset Interval
Manual restart of the measurement and sta-
tistics interval
BOOLEAN
RW
0x00 (0
dec
)
F800:12
Measurement Range
Filter setting for determining the fundamental
permitted values:
UINT32
RW
0x00000000 (0
dec
)
0
25..65 Hz (default)
1
25..400 Hz
2
12..45 Hz
F800:13
Frequency Source
Source of the system frequency
permitted values:
BIT1
RW
0x00000000 (0
dec
)
0
Channel 1 (default)
1
Channel 2
2
Channel 3
F800:15
Inaccurate Threshold
Voltage
Limit value for the warning bit: Inaccurate
Voltage
REAL32
RW
0x3FDC28F6
(1071393014
dec
)
Содержание EL34 Series
Страница 1: ...Documentation EL34xx 3 phase energy and power measurement terminals 1 5 2019 09 05 Version Date ...
Страница 2: ......
Страница 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Страница 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Страница 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Страница 103: ...Commissioning EL34xx 103 Version 1 5 Fig 105 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...
Страница 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Страница 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Страница 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Страница 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Страница 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Страница 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Страница 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Страница 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Страница 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...