7.5
Power measurement at three-phase motors controlled
by a frequency converter
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, voltage-free state before starting mounting, disassembly or
wiring of the Bus Terminals!
The example illustrates power measurement at several three-phase motors that are controlled by a
frequency converter (AC converter), e.g. at a conveyor system. Each motor is monitored by a EL3443.
Fig. 167: Application example with frequency converter
The electrical isolation of the three-phase-transformer (Yy0) operated by the voltage circuit of the power
measurement terminals enables measurement after the frequency converter.
Measuring error in the lower frequency range
If the power measurement takes place after the frequency converter, a larger measuring error is
possible in the lower frequency range, particularly for voltage measurement. This error also affects
the power calculation.
The three-phase transformer should have a ratio of 1:1. It must not cause a phase shift of the signal! Since
high-frequency components only have little influence on the motors, any distortions caused by the three-
phase transformer have little effect on the practical measurement during the transfer of the harmonics
created by the frequency converter.
The power distribution is mapped very well by using a dedicated power measurement terminal for each
motor. Excessive current consumption of an individual motor can be detected in good time.
It is not possible to use this method for measuring direct voltage/DC (e.g. holding currents of synchronous
motors)! Practical results can be obtained for voltages/currents with a frequency above 12 Hz, depending on
the three-phase transformer and current transformers used.
CAUTION
The terminal points N must be grounded!
Due to the electrical isolation through the three-phase transformer, the terminal points N of the power mea-
surement terminals have to be grounded, in order to avoid dangerous overvoltages in the event of a fault in
a current transformer!
Содержание EL34 Series
Страница 1: ...Documentation EL34xx 3 phase energy and power measurement terminals 1 5 2019 09 05 Version Date ...
Страница 2: ......
Страница 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Страница 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Страница 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Страница 103: ...Commissioning EL34xx 103 Version 1 5 Fig 105 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...
Страница 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Страница 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Страница 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Страница 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Страница 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Страница 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Страница 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Страница 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Страница 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...