Commissioning
EL34xx
195
Version: 1.5
Index FA00 PMX Diag data
Index (hex) Name
Meaning
Data type
Flags
Default
FA00:0
PMX Diag data
Max. subindex
UINT8
RO
0x13 (19
dec
)
FA00:11
Min CPU Die Temper-
ature
Minimum CPU temperature measured so far
REAL32
RO
0x00000000 (0
dec
)
FA00:12
Max CPU Die Tem-
perature
Maximum CPU temperature measured so far
REAL32
RO
0x00000000 (0
dec
)
FA00:13
EBUS Voltage
Current E-bus voltage
REAL32
RO
0x00000000 (0
dec
)
6.7.3.7
Standard objects
Standard objects (0x1000-0x1FFF)
The standard objects have the same meaning for all EtherCAT slaves.
Index 1000 Device type
Index (hex) Name
Meaning
Data type
Flags
Default
1000:0
Device type
Device type of the EtherCAT slave: The Lo-Word
contains the CoE profile used (5001). The Hi-Word
contains the module profile according to the modular
device profile.
UINT32
RO
0x01551389
(22352777
dec
)
Index 1008 Device name
Index (hex) Name
Meaning
Data type
Flags
Default
1008:0
Device name
Device name of the EtherCAT slave
STRING
RO
EL34xx
Index 1009 Hardware version
Index (hex) Name
Meaning
Data type
Flags
Default
1009:0
Hardware version
Hardware version of the EtherCAT slave
STRING
RO
Index 100A Software Version
Index (hex) Name
Meaning
Data type
Flags
Default
100A:0
Software version
Firmware version of the EtherCAT slave
STRING
RO
Index 100B Bootloader version
Index (hex) Name
Meaning
Data type
Flags
Default
100B:0
Bootloader version
Bootloader version
STRING
RO
Index 1018 Identity
Index (hex) Name
Meaning
Data type
Flags
Default
1018:0
Identity
Information for identifying the slave
UINT8
RO
0x04 (4
dec
)
1018:01
Vendor ID
Vendor ID of the EtherCAT slave
UINT32
RO
0x00000002 (2
dec
)
1018:02
Product code
Product code of the EtherCAT slave
UINT32
RO
0x0D733052
(225652818
dez
)
1018:03
Revision
Revision number of the EtherCAT slave; the low
word (bit 0-15) indicates the special terminal number,
the high word (bit 16-31) refers to the device descrip-
tion
UINT32
RO
0x00000000 (0
dec
)
1018:04
Serial number
Serial number of the EtherCAT slave; the low byte
(bit 0-7) of the low word contains the year of produc-
tion, the high byte (bit 8-15) of the low word contains
the week of production, the high word (bit 16-31) is 0
UINT32
RO
e.g. 0x00001E06
(KW 30/2006)
Содержание EL34 Series
Страница 1: ...Documentation EL34xx 3 phase energy and power measurement terminals 1 5 2019 09 05 Version Date ...
Страница 2: ......
Страница 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Страница 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Страница 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Страница 103: ...Commissioning EL34xx 103 Version 1 5 Fig 105 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...
Страница 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Страница 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Страница 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Страница 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Страница 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Страница 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Страница 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Страница 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Страница 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...