Commissioning
EL34xx
224
Version: 1.5
Index F60F PMX Total System Angles
Index (hex) Name
Meaning
Data type
Flags
Default
F60F:0
PMX Total System
Angles
Max. subindex
UINT8
RO
0x15 (21
dec
)
F60F:11
Voltage Angle L1 L2
Angle between the phase voltages of L1 and L2
REAL32
RO
0x00000000 (0
dec
)
F60F:12
Voltage Angle L1 L3
Angle between the phase voltages of L1 and L3
REAL32
RO
0x00000000 (0
dec
)
F60F:13
Current Angle L1
Phase angle of the current of L1
REAL32
RO
0x00000000 (0
dec
)
F60F:14
Current Angle L2
Phase angle of the current of L2
REAL32
RO
0x00000000 (0
dec
)
F60F:15
Current Angle L3
Phase angle of the current of L3
REAL32
RO
0x00000000 (0
dec
)
Index F610 PMX Total System
Index (hex) Name
Meaning
Data type
Flags
Default
F610:0
PMX Total System
Max. subindex
UINT8
RO
0x15 (21
dec
)
F610:11
Positive Sequence
Voltage of the co-system
REAL32
RO
0x00000000 (0
dec
)
F610:12
Negative Sequence
Voltage of the opposing system
REAL32
RO
0x00000000 (0
dec
)
F610:13
Zero Sequence
Zero system voltage
REAL32
RO
0x00000000 (0
dec
)
Index F611 PMX Total Statistic Power Fundamental
Index (hex) Name
Meaning
Data type
Flags
Default
F611:0
PMX Total Statistic
Power Fundamental
Max. subindex
UINT8
RO
0x18 (24
dec
)
F611:10
Active Power Avg
Fund
Average total active power of the fundamental of the
last interval in W
REAL32
RO
0x00000000 (0
dez
)
F611:11
Active Power Min
Fund
Total active power minimum of the fundamental in
the last interval in W
REAL32
RO
0x00000000 (0
dez
)
F611:12
Active Power Max
Fund
Total active power maximum of the fundamental in
the last interval in W
REAL32
RO
0x00000000 (0
dez
)
F611:13
Apparent Power Avg
Fund
Average total apparent power of the fundamental of
the last interval in VA
REAL32
RO
0x00000000 (0
dez
)
F611:14
Apparent Power Min
Fund
Total apparent power minimum of the fundamental in
the last interval in VA
REAL32
RO
0x00000000 (0
dez
)
F611:15
Apparent Power Max
Fund
Total apparent power maximum of the fundamental in
the last interval in VA
REAL32
RO
0x00000000 (0
dez
)
F611:16
Reactive Power Avg
Fund
Average total reactive power of the fundamental of
the last interval in var
REAL32
RO
0x00000000 (0
dez
)
F611:17
Reactive Power Min
Fund
Total reactive power minimum of the fundamental in
the last interval in var
REAL32
RO
0x00000000 (0
dez
)
F611:18
Reactive Power Max
Fund
Total reactive power maximum of the fundamental in
the last interval in var
REAL32
RO
0x00000000 (0
dez
)
6.7.4.5
Output data
Index F700 PMX Variant Value Out
Index (hex) Name
Meaning
Data type
Flags
Default
F700:0
PMX Variant Value
Out
Max. subindex
UINT8
RO
0x14 (20
dec
)
F700:11
Index 1 REAL
Request for variable output value 1 (REAL)
Can be used for all non-energy values (details see
settings)
UINT16
RO
0x0000 (0
dec
)
F700:12
Index 2 REAL
Request for variable output value 2 (REAL)
Can be used for all non-energy values (details see
settings)
UINT16
RO
0x0000 (0
dec
)
F700:13
Index 3 REAL
Request for variable output value 3 (REAL)
Can be used for all non-energy values (details see
settings)
UINT16
RO
0x0000 (0
dec
)
F700:14
Index 4 ULINT
Request for variable output value 4 (ULINT)
Can be used for all energy values (which are output
as ULINT): 45-59 and 1069-1083
UINT16
RO
0x0000 (0
dec
)
Содержание EL34 Series
Страница 1: ...Documentation EL34xx 3 phase energy and power measurement terminals 1 5 2019 09 05 Version Date ...
Страница 2: ......
Страница 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Страница 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Страница 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Страница 103: ...Commissioning EL34xx 103 Version 1 5 Fig 105 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...
Страница 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Страница 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Страница 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Страница 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Страница 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Страница 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Страница 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Страница 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Страница 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...