Commissioning
EL34xx
245
Version: 1.5
Index 1C32 SM output parameter
Index
Name
Meaning
Data type
Flags
Default
1C32:0
SM output parameter Synchronization parameters for the outputs
UINT8
RO
0x20 (32
dec
)
1C32:01
Sync mode
Current synchronization mode:
0: Free Run
1: Synchron with SM 2 Event
2: DC-Mode - Synchron with SYNC0 Event
3: DC-Mode - Synchron with SYNC1 Event
UINT16
RW
0x0000 (0
dec
)
1C32:02
Cycle time
Cycle time (in ns):
Free Run: Cycle time of the local timer
Synchron with SM 2 Event: Master cycle time
DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x0016E360
(1500000
dec
)
1C32:03
Shift time
Time between SYNC0 event and output of the out-
puts (in ns, DC mode only)
UINT32
RO
0x00000384 (900
dec
)
1C32:04
Sync modes sup-
ported
Supported synchronization modes:
Bit 0 = 1: free run is supported
Bit 1 = 1: synchronous with SM 2 event is supported
Bit 2-3 = 01: DC mode is supported
Bit 4-5 = 10: Output shift with SYNC1 event (only DC
mode)
Bit 14 = 1: dynamic times (measurement through
writing of 1C32:08)
UINT16
RO
0x0805 (2053
dec
)
1C32:05
Minimum cycle time
Minimum cycle time (in ns)
UINT32
RO
0x0007A120
(500000
dec
)
1C32:06
Calc and copy time
Minimum time between SYNC0 and SYNC1 event (in
ns, DC mode only)
UINT32
RO
0x00000384 (900
dec
)
1C32:07
Minimum delay time
UINT32
RO
0x00000384 (900
dec
)
1C32:08
Command
0: Measurement of the local cycle time is stopped
1: Measurement of the local cycle time is started
The entries 1C32:03, 1C32:05, 1C32:06, 1C32:09,
1C33:03, 1C33:06, 1C33:09 are updated with the
maximum measured values.
For a subsequent measurement the measured val-
ues are reset
UINT16
RW
0x0000 (0
dec
)
1C32:09
Maximum delay time
Time between SYNC1 event and output of the out-
puts (in ns, DC mode only)
UINT32
RO
0x00000384 (900
dec
)
1C32:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or
the next cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C32:0D
Shift too short counter Number of occasions that the interval between
SYNC0 and SYNC1 event was too short (DC mode
only)
UINT16
RO
0x0000 (0
dec
)
Содержание EL34 Series
Страница 1: ...Documentation EL34xx 3 phase energy and power measurement terminals 1 5 2019 09 05 Version Date ...
Страница 2: ......
Страница 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Страница 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Страница 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Страница 103: ...Commissioning EL34xx 103 Version 1 5 Fig 105 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...
Страница 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Страница 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Страница 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Страница 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Страница 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Страница 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Страница 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Страница 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Страница 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...