Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
0: Free Run
1: Synchron with SM 3 Event (no outputs available)
2: DC - Synchron with SYNC0 Event
3: DC - Synchron with SYNC1 Event
34: Synchron with SM 2 event (outputs available)
UINT16
RW
0x0000 (0
dec
)
1C33:02
Cycle time
as 1C32:02
UINT32
RW
0x0016E360
(1500000
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000384 (900
dec
)
1C33:04
Sync modes sup-
ported
Supported synchronization modes:
Bit 0: free run is supported
Bit 1: Synchron with SM 2 Event is supported (out-
puts available)
Bit 1: Synchron with SM 3 Event is supported (no
outputs available)
Bit 2-3 = 01: DC mode is supported
Bit 4-5 = 01: Input shift through local event (outputs
available)
Bit 4-5 = 10: Input shift with SYNC1 event (no outputs
available)
Bit 14 = 1: dynamic times (measurement through
writing of 1C32:08 or 1C33:08)
UINT16
RO
0x0805 (2053
dec
)
1C33:05
Minimum cycle time
as 1C32:05
UINT32
RO
0x0007A120
(500000
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32
RO
0x0007A120
(500000
dec
)
1C33:07
Minimum delay time
UINT32
RO
0x00000384 (900
dec
)
1C33:08
Command
as 1C32:08
UINT16
RW
0x0000 (0
dec
)
1C33:09
Maximum delay time
Time between SYNC1 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000384 (900
dec
)
1C33:0B
SM event missed
counter
as 1C32:11
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
as 1C32:12
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter as 1C32:13
UINT16
RO
0x0000 (0
dec
)
Index F000 Modular device profile
Index (hex) Name
Meaning
Data type
Flags
Default
F000:0
Modular device profile Largest subindex of this object
UINT8
RO
0x02
F000:01
Module index dis-
tance
Index distance of the objects of the individual chan-
nels
UINT16
RW
0x0010 (16
dec
)
F000:02
Maximum number of
modules
Number of channels
UINT16
RW
0x0003 (3
dec
)
Index F008 Code word
Index (hex) Name
Meaning
Data type
Flags
Default
F008:0
Code word
reserved
UINT32
RW
0x00000000 (0
dec
)
Code Word
The vendor reserves the authority for the basic calibration of the terminals. The code word is there-
fore at present reserved.
Содержание EL34 Series
Страница 1: ...Documentation EL34xx 3 phase energy and power measurement terminals 1 5 2019 09 05 Version Date ...
Страница 2: ......
Страница 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Страница 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Страница 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Страница 103: ...Commissioning EL34xx 103 Version 1 5 Fig 105 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...
Страница 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Страница 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Страница 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Страница 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Страница 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Страница 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Страница 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Страница 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Страница 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...