Application

The 22Z570 Terminal Box is a further development of 

the reliable KRIWAN motor protectors.
The 22Z570 Terminal Box incorporates an INT69 

I2 Diagnose and INT185 Current Transformer to 

protect the compressor against thermal and electrical 

overload. 
The 22Z570 Terminal Box is designed to replace 

existing terminal boxes on Carlyle 06D and 06CC 

compressors. For 4 or 2 cylinder compressors, a 

mounting spacer may be needed.

Functional description (with PTC thermistors)

Up to 9 PTC-sensors according to DIN 44081/082 

with different nominal response temperatures can be 

connected in series to the measuring circuit. If the 

temperature in one of the areas monitored exceeds 

the nominal response temperature of the respective 

PTC-sensor, the sensor resistance increases and the 

INT69 I2 switches off. See data sheet of INT69 I2 for 

additional information.

One phase of the three phase power must go 

through the INT185 current transformer. If the current 

going through the current transformer exceeds the 

programmed amps of the INT69 I2, the INT69 I2 

switches off. See data sheet of INT185 for additional 

information. 

Installation

This unit is designed to be mounted on Carlyle 

06D and 06CC compressors. Do not use on other 

compressor models.

22Z570 Terminal Box

06D Terminal Box 

This unit must be installed and connected 

to a compressor that has a motor with PTC 

sensors properly installed in series on each 

phase.

!

This unit must be programmed to the proper 

MCC trip amps of the compressor. It comes

preprogrammed with a trip amp setting of 4A 

as a default.

!

To ensure proper electrical grounding, this unit 

must be installed to the compressor using two 

bolts with star lock washers. Star lock washers 

should penetrate any paint to ensure a good 

electrical connection.

!

The mounting, maintenance and operation are 

to be carried out by an electrician. The valid 

European and national standards for connecting 

electrical equipment and cooling installations 

have to be observed. Connected sensors and 

connection lines that extend from the terminal 

box have to feature at least a basic insulation.

!

L

N

1

2

3

14

11

1
2
3

To Control 

Circuit

120/240V

1

2

3

8

9

Field Connection

Field Connection

GND

Field Connection

Picture

L

N

1

2

3

14

11

1
2
3

To Control 

Circuit

120/240V

1

2

3

8

9

Field Connection

Field Connection

GND

Field Connection

Wiring diagram - 5 Pin Terminal Plate (PTC only)

Wiring diagram - 6 Pin Terminal Plate

7

PTC

Thermostat

Pins 8-9

PTC

Wiring for PTC Overloads & Instuctions

 