Index 0x80nD AI Advanced Settings (n=0: Channel 1, n=1: Channel 2)
Index
(hex)
Name
Meaning
Data type
Flags Default
80nD:0
AI Advanced
Settings
Maximum subindex
UINT8
RO
0x11 (17
dez
)
80nD:11
Input Type
Allowed values:
UINT16
RW
0x14 (20
dez
)
0x13 (19
dez
) I 4-20mA
0x14 (20
dez
) I 4-20mA NAMUR
80nD:12
Scaler
Scaling range, allowed values:
UINT16
RW
0x0000 (0
dez
)
0x00
Extended Range
0x03
0x03 Legacy Range
80nD:17
Low Range Error
Lower threshold for setting the error bit
and error led
INT32
RW
Dependent on
80nD:11
80nD:18
High Range Error Upper threshold for setting the error bit
and error led
INT32
RW
Dependent on
80nD:11
Index 0x80n0 HART Settings (n=8: Channel 1, n=9: Channel 2)
Index (hex)
Name
Meaning
Data type
Flags
Default
80n0:0
HART
Settings
Maximum subindex
UINT8
RO
0x06 (6
dez
)
80n0:01
Preamble
Preamble length:
UINT8
RW
0x00 (0
dez
)
Automatic
allocation
0
Allowed
values
5…20
80n0:02
MasterMode Allowed values:
UINT8
RW
0x00 (0
dez
)
Primary
0
Secondary
1
80n0:03
PollingAddre
ss
Allowed values:
UINT8
RW
0x00 (0
dez
)
0…63
80n0:04
PollingTime
Unit in seconds,
allowed values:
UINT8
RW
0x03 (3
dez
)
1…64
80n0:05
MaxRetry
Allowed values:
UINT8
RW
0x03 (3
dez
)
3…10
80n0:06
MasterCtrl
reserved
UINT8
RW
0x00 (0
dez
)