HART
EL3182
121
Version: 1.2
Reading is initiated by entering the HART command. If the slave supports the feature, the read length and
the data are returned.
For a write call the command also has to be entered, plus the user data to be written (without header and
CRC). The structure of the data to be used is described in the corresponding HART documentation (e.g.
"Universal Command Specification").
If a HART command has user data in both directions (i.e. for reading and writing), the ReadWrite function
can be used.
The commands can be issued directly via ADS. IdxGrp = 0xF302 and IdxOffs = Cmd should be used for this
purpose.
Содержание EL3182
Страница 2: ......
Страница 46: ...Commissioning EL3182 46 Version 1 2 Fig 43 Incorrect driver settings for the Ethernet port...
Страница 57: ...Commissioning EL3182 57 Version 1 2 Fig 62 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 94: ...Commissioning EL3182 94 Version 1 2 Index 0x1C32 SM output parameter...