Product overview
EL3182
14
Version: 1.2
2.2
Technical data
Technical data
EL3182
Number of inputs
2
Technology
HART Version 7
Signal type
single-ended
Signal current
4…20 mA
Power supply
via the E-bus
Internal resistance
typ. 250 Ω
Input filter limit frequency
25 Hz
Dielectric strength
max. 30 V
Measuring range, technical
generally 107 % of the nominal measuring range
Resolution
16 bit (incl. sign)
Measuring error
< ±0.3 % (relative to full scale value)
Distributed clocks
Yes
Electrical isolation
500 V (E-bus/signal voltage)
Current consumption power contacts
-
Current consumption E-bus
typ. 130 mA
Bit width in the process image
8 byte, HART: 28 byte per channel as option
Special features
• Standard and compact process image
• Activatable FIR/IIR filters
• Limit value monitoring
• ExtendedRange 107 %
• NE43 NAMUR
Max. allowed output current (Uv1 / Uv2)
typ. 150 mA (per connector)
Weight
approx. 60 g
Permissible ambient temperature range during
operation
-25°C ... + 60°C
Permissible ambient temperature range during
storage
-40°C ... + 85°C
Relative humidity
95 %, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12
mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
according to EN 60068-2-6/EN 60068-2-27,
see also
with increased mechanical load capacity
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
2.3
Start
For commissioning:
• mount the EL3182 as described in the chapter
• configure the EL3182 in TwinCAT as described in chapter
Содержание EL3182
Страница 2: ......
Страница 46: ...Commissioning EL3182 46 Version 1 2 Fig 43 Incorrect driver settings for the Ethernet port...
Страница 57: ...Commissioning EL3182 57 Version 1 2 Fig 62 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 94: ...Commissioning EL3182 94 Version 1 2 Index 0x1C32 SM output parameter...