Commissioning
EL3182
103
Version: 1.2
Bit value
Meaning
Description
0x80
Device Malfunction
The device detected a serious error or failure that
compromises device operation.
0x40
Configuration
Changed
An operation was performed that changed the device’s
configuration.
0x20
Cold Start
A power failure or Device Reset has occured.
0x10
More Status Available
More status information is available via Command 48, Read
Additional Status Information.
0x08
Loop Current Fixed
The Loop Current is being held at a fixed value and is not
responding to process variations.
0x04
Loop Current
Saturated
The Loop Current has reached its upper (or lower) endpoint
limit and cannot increase (or decrease) any further.
0x02
Non-Primary Variable
Out of Limits
A Device Variable not mapped to the PV is beyond its
operating limits.
0x01
Primary Variable Out
of Limits
The PV is beyond its operating limit.
PV = Primary Variable
5.4.5
Settings and operating modes
5.4.5.1
Presentation, index 0x80n0:02
The measured value output is set in factory to two's complement representation (signed integer).
Index 0x80n0:02 offers the possibility to change the method of representation of the measured value.
Signed integer representation
The negative output value is represented in two’s complement (n 1).
Maximum representation range for 16 bits = -763
dec
to +32425
dec
4..20 mA
(NAMUR)
Decimal
Hexadecimal
-
32767
0x7FFF
21 mA
32425
0x7EAC
20,5 mA
31472
0x7A20
20 mA
30518
0x7736
4 mA
0
0x0000
3,8 mA
-381
0xFE83
3,6 mA
-763
0xFD05
-
-32768
0x8000