80-0042-00, Rev. 06.9
Action on Loss of Demand Stays in place or moves to predetermined position with ac power
Input Signal (Option 7)
supplied.
Stall Protection (Option 7)
If the motor tries to run in one direction for more than approx. 136
seconds, it will shut off.
Stall Relay Contacts
Form A, 10 volt-amps at 120 V ac or dc
(Option 7)
Action on Stall (Option 7)
Motor power is turned off when relay contacts open (after 136
seconds of stall). Remote signal is available.
Travel Limit Switches
Two Form C (Retract and Extend), field-adjustable.
Rated 10 A, 125/150 Vac; .5 A, 125 Vdc; .25 A, 150 Vdc.
Auxiliary Switches
Two Form C rated for 1 A, 250 V ac., field-adjustable.
Rated 10 A, 125/150 Vac; .5 A, 125 Vdc; .25 A, 150 Vdc.
Handswitch (Option 7)
Permits local electrical operation, independent of Demand input
signal.
Handwheel
Provides manual operation without electrical power.
Customer Wiring
Terminals accommodate up to 12 AWG (3.31 mm
2
).
Motor
120 V ac, single-phase, no burnout, non-coasting. Capable of 60
starts per minute.
Enclosure
Precision-machined aluminum alloy, painted with corrosion-
resistant polyurethane paint, to provide a rugged, dust-tight,
weatherproof enclosure. Type 4X; IP66.* Actuators designed for
hazardous locations are also available.
Mounting Orientation
Can be mounted in any orientation.
Standards*
CSA Certified
CE Compliant
*
NOTE: May not be available with all options and models. For more information, or to inquire about