  Power and signal wires must be routed to the 

actuator separately and be either shielded cables 

or installed in conductive conduit and/or cable trays.

  Shielded, twisted pair cables should be used 

for signal connections to avoid being affected by 

electrical noise.  These signal wires, based on Noise 

Susceptibility Level (NSL) per IEEE-518, fall into the 

level 1 classification.  A braided shield will be more 

effective than a wrapped foil shield.  Signal wire 

shields should be connected to the actuator casting 

grounding screw.  If grounding at the signal source 

is required, then the shield should not be grounded 

at the drive.  Raceways such as conduits and trays 

have to be grounded at both ends to properly meet 

immunity requirements. 

  A large, clearly labeled terminal block in the 

actuator is enclosed in a separate, gasketed metal 

enclosure.  Terminals will accommodate up to 12 

AWG (3.31 mm

2

) wiring.

  

CAUTION

Always close covers immediately 

after installation or service to prevent 

moisture or other foreign matter 

from entering the actuator.

  Refer to the wiring diagram furnished with your 

Beck  actuator  for  proper AC  power  and  signal 

connections.  It is advisable to provide normal short 

circuit protection on the AC power line.  A copy of 

the wiring diagram is shipped with each actuator 

and is fastened to the inside of the terminal block 

cover.  If there is no wiring diagram available, you 

may obtain a copy from Beck by providing the serial 

number of your drive.

  Your Beck actuator has been supplied to match 

the signal source in your control loop.  If it does not 

match, a 250 ohm input resistor may be added or 

removed to obtain the proper match.  Consult the 

factory for details.

  For  maximum  safety,  and  to  comply  with 

national  and  international  standards,  the  Beck 

actuator body is required to be grounded.  Use 

one of the two grounding terminals in the wiring 

compartment  of  the  actuator  to  make  this 

connection.    Wire  size  12 AWG  (3.31  mm

2

)  is 

recommended for this purpose.

CONDUIT ENTRIES

 

Conduits  are  provided  for  power  and  signal 

wiring.    Temporary  plugs  are  installed  in  the 

conduits  at  the  factory  for  shipping  only  and  are 

not intended for permanent use.  Prior to actuator 

operation, all conduit entrances must be properly 

sealed in accordance with National Standards or 

Regulatory Authorities.

SAFETY PRECAUTIONS

WARNING

Installation and service instructions 

are  for  use  by  qualified  personnel 

only.  To avoid injury and electric 

shock, do not perform any servicing 

other than that contained in this 

manual.  Please read and understand 

the appropriate sections in this 

manual before attempting to install 

or operate your drive.

CAUTION

Hot surfaces!  Surfaces of equipment 

may be at an elevated temperature 

depending on operating conditions 

and environment.  Allow to cool 

before servicing.

STORAGE INFORMATION

  Beck actuators should be stored in their shipping 

cartons in a clean, dry area.

  If it is necessary to store actuators outdoors for 

a long period of time, they should be stored above 

ground and covered with a waterproof cover.  Do not 

stack cartons.  Stored actuators should be checked 

periodically to ensure no condensation has formed 

in electronic and terminal compartments.  Moisture 

damage while in storage is not covered by warranty.

UNPACKING

  Group 42 actuators are shipped in standardized 

cardboard shipping containers and secured to a 

wooden platform.  

INSTALLATION—ELECTRICAL

NOTE:  All Beck actuators are shipped from 

the factory ready for installation; no electrical 

adjustments are required before placing them 

in operation.  Each actuator is set up and 

calibrated  to  the  customer’s  specifications 

that were written into the equipment order.

  Two N.P.T. conduit connections are provided for 

power and signal wiring to the drive.  One 3/4" conduit 

is provided for signal wiring connections, and the 

other 3/4" conduit is provided for power and auxiliary 

switch connections.  A sealant must be used on 

threaded conduit connections to keep moisture out.  

Conduits should be routed from below the actuator so 

that condensation and other contaminants entering 

the conduit cannot enter the drive.

INSTALLATION

Содержание 42-103

Страница 1: ...80 0042 00 Rev 06 9 INSTRUCTION MANUAL 42 107 42 105 42 103 MODELS R E L E C T R I C A C T U A T O R S F O R I N D U S T R I A L P R O C E S S C O N T R O L...

Страница 2: ...ns 11 Calibration 12 Travel Limit Switch Adjustment 12 Setting Auxiliary Switches 14 Changing Direction of Travel 15 Feedback Signal 16 Demand Input Signal 18 Loss of Signal Function 19 Deadband Adjus...

Страница 3: ...ntenance Ideally suited for harsh industrial environments the Group 42 handles long stroke applications requiring up to 1 000 lbs 4 450 N of thrust The design employs a highly efficient ball screw cou...

Страница 4: ...ne current from a remote controller or manual switches 3 Modulating analog control option 7 Onboard actuator control electronics position output proportionally to mA Demand input signal Demand Input S...

Страница 5: ...adjustable Rated 10 A 125 150 Vac 5 A 125 Vdc 25 A 150 Vdc Handswitch Option 7 Permits local electrical operation independent of Demand input signal Handwheel Provides manual operation without electr...

Страница 6: ...7 11 279 28 19 32 726 46 19 32 1183 69 31 2 17 32 DIA 64 7 25 32 198 8 7 32 209 ALLOW 2 3 4 70 FOR REMOVAL 2 1 4 57 3 11 32 85 L DIMENSION 3 8 10 1 1 16 27 SEE TABLE REAR CLEVIS HOLE DIAMETER 1 25 SEE...

Страница 7: ...n conductive conduit and or cable trays All signal and power connections are made on the terminal board Typical wiring connections for each Group 42 control option are described on the following pages...

Страница 8: ...nal 12 The loop powered position feedback signal must be connected to a 2 wire type analog input that provides a dc voltage over the signal wires a dc voltage power supply must be wired in series with...

Страница 9: ...d to terminal 15 Direct AC Control with Actuator Powered Position Feedback Signal Customer must supply three wires to directly control the actuator motor direction One 120 V ac line to run Extend term...

Страница 10: ...m2 is recommended for this purpose CONDUIT ENTRIES Conduits are provided for power and signal wiring Temporary plugs are installed in the conduits at the factory for shipping only and are not intended...

Страница 11: ...put shaft travels through its desired stroke Note that the F extend and R retract LEDs on the control board light to indicate the direction of travel of the output shaft The LEDs remain lit when the u...

Страница 12: ...ine voltage and auxiliary switches are disconnected from external power sources Setting the Retract Travel Limit Switch S3 1 Remove the control module cover 2 Retract the output shaft to the desired t...

Страница 13: ...witch wires remove the two wires from the extend limit switch top switch and attach the meter across these contacts See Fig 3 at right Rotate the cam see Fig 2 at right until the meter shows no contin...

Страница 14: ...eter and actuator power 8 Extend Retract the output shaft again to the desired switch position If the contacts close the switch is properly set 9 Replace the control module cover SETTING AUXILIARY SWI...

Страница 15: ...to the power transformer see Figure 4 this page 3 For extend output shaft travel on an increasing signal the orange wire must be on the common terminal of S4 and the brown wire on the common terminal...

Страница 16: ...n TABLE 1 below FEEDBACK SIGNAL CALIBRATION For 4 wire feedback only All Group 42 actuators are shipped with the Option 7 Terminal Board Figure 5 TABLE 1 R4 F1 R3 VR2 VR1 TB1 TB2 22 4001 13 R 2 1 2 1...

Страница 17: ...put 14 Move the output shaft towards the maximum input signal position with a 249 ohm resistor To convert a 1 5 volt configuration to 4 20 milliamps remove the 249 ohm resistor and replace it with a 1...

Страница 18: ...sition if the travel is set to retract Allow the over travel limit switch to de energize the motor at the limit 16 Turn trim potentiometer R38 counterclockwise until the output signal is 20 05 mA 001...

Страница 19: ...n function in two ways 1 Actuator will stay in its last position when the signal was lost 2 Actuator will move to a position determined by the setting of trim potentiometer R16 The LOS function will s...

Страница 20: ...to stall will be decreased to 68 seconds which may be shorter than the full stroke travel time of some actuators R20 Parallel Resistor Effective Resistance Dead band 1 000 000 1 0 1 000 000 2 000 000...

Страница 21: ...he factory see back cover for factory contact information CUSTOMER KIT PART NUMBER Capacitor Replacement 6 0Nm 72 RPM Motor 60Hz 12 8064 10 Capacitor Replacement 6 0Nm 72 RPM Motor 50Hz 12 8064 20 Res...

Страница 22: ...itch failure a b c d Check control board calibration See calibration procedure p 18 Readjust limit switches See limit switch adjustment p 12 Restore input signal to actuator Replace limit switch Conta...

Страница 23: ...laims damages costs or liabilities including but not limited to attorney s fees and other legal expenses whether on account of negligence or otherwise except those claims based solely upon the neglige...

Страница 24: ...02 19 11 TERRY DRIVE NEWTOWN PENNSYLVANIA 18940 USA PHONE 215 968 4600 FAX 215 860 6383 E MAIL sales haroldbeck com www haroldbeck com HAROLD BECK SONS INC R Made in USA...

Отзывы: