16

80-0042-00, Rev. 06.9

feedback calibrated for full output shaft travel unless 

otherwise  specified  at  time  of  order.  Feedback 

signal calibration is necessary to ensure that the 

signal current or voltage correctly corresponds to 

the actuator output shaft position.    

CHANGING FEEDBACK SIGNAL TYPE

  The feedback signal may be specified as 4-20 

milliamps or 1-5 volts when ordered or it may be 

changed at installation, using the following methods.

  FOR OPTION 7:  To convert a 4-20 milliamp 

configuration to 1-5 volts, remove the diode from 

position  R2  on  the  terminal  board  and  replace 

FEEDBACK SIGNAL OPTIONS 

(OPTIONS 5 & 7 ONLY)

  The feedback signal is an analog voltage or 

current signal proportional to the position of the 

drive’s output shaft.  It may be used for remote 

position  indication  or  for  automatic  control 

loop  feedback.   Actuators  with  Options  5  or  7 

may  be  field  connected  to  function  as  a  two 

wire transmitter or as a four wire active current 

source.  This circuit configuration is determined 

by  the  position  of  Jumper  Plug  J5/J6  located 

on  the  control  board  (J-J5  for  2-wire,  J-J6  for 

4-wire).    See  Figure  6  or  7  for  J5/J6  location.  

Unless otherwise specified at the time of order, 

all  Group  42  actuators  are  shipped  with  the 

feedback  circuit  configured  as  a  4-wire  system.  

Also,  all  Option  7  models  are  shipped  with  a 

249 ohm resistor (R5) mounted between output 

signal terminals 13 and 14.  This resistor is used 

to ensure proper operation of the control board 

when the feedback signal is not connected to a 

control  room

 

indicator.   A  summary  of  position 

feedback  options,  output  signal  ranges  and 

control board and terminal board part numbers is 

provided in TABLE 1, below.

FEEDBACK SIGNAL & CALIBRATION

For 4‑wire feedback only

  All  Group  42  actuators  are  shipped  with  the 

Option 7 Terminal Board

Figure 5

TABLE 1

R4

F1

R3

VR2

VR1

TB1

TB2

22-4001-13

R 2

1

2

1

2

TP2

15

14

13

12

TP1

11

15

14

3

4

13

12

10

5

9

6

3

4

5

6

11

10

8

7

9

8

7

R1

R5

Fdbk. Control Signal Config. Ext. Pwr.

Fdbk. Sig. 

Conn.

Jumper

Loc.

Max. 

Ext.

Load

Input

Fdbk.

Input Output

Meter Conn. for

Signal Cal.

System Option Input

Output Supply Plus Minus

Res. R1 Res. R2 Res. Ω Res. Ω Plus

Minus

Milliameter Connection

2-Wire

5

120 V 4-20 mA <35 V

15

14

J-J5

300Ω

--

Diode

--

>1 M

14

Cust. - (Series)

2-Wire

5

120 V 4-20 mA >36 V

14

15

J-J5

800Ω

--

Open

--

>1 M

15

Cust. - (Series)

2-Wire

7

1-5 V 4-20 mA <35 V

15

14

J-J5

300Ω

--

Diode

2 M

>1 M

14

Cust. - (Series)

2-Wire

7

1-5 V 4-20 mA >36 V

14

15

J-J5

800Ω

--

Open

2 M

>1 M

15

Cust. - (Series)

2-Wire

7

4-20 mA 4-20 mA <35 V

15

14

J-J5

300Ω

249Ω

Diode

249

>1 M

14

Cust. - (Series)

2-Wire

7

4-20 mA 4-20 mA >36 V

14

15

J-J5

800Ω

249Ω

Open

249

>1 M

15

Cust. - (Series)

*4-Wire

5

120 V 4-20 mA 120 V

14

13

J-J6

500Ω

--

Diode

--

>1 M

14

Cust. + (Series)

4-Wire

7

1-5 V 4-20 mA 120 V

14

13

J-J6

500Ω

--

Diode

2 M

>1 M

14

Cust. + (Series)

*4-Wire

7

4-20 mA 4-20 mA 120 V

14

13

J-J6

500Ω

249Ω

Diode

249

>1 M

14

Cust. + (Series)

Voltmeter Connection

4-Wire

5

120 V

1-5 V

120 V

14

13

J-J6 0.4 mA

--

249Ω

--

249

14

13 (Parallel)

4-Wire

7

1-5 V

1-5 V

120 V

14

13

J-J6 0.4 mA

--

249Ω

2 M

249

14

13 (Parallel)

4-Wire

7

4-20 mA 1-5 V

120 V

14

13

J-J6 0.4 mA 249Ω

249Ω

2 M

249

14

13 (Parallel)

Control Option 5 = Control Board 22-4001-10 & Terminal Board 22-4001-07.

Control Option 7 = Control Board 22-4001-17 or 22-5001-21 (22-5001-21 supersedes 22-4001-17) & Terminal Board 22-4001-13.

Note:  For Split Range Operation, 1-5 V dc input can be calibrated 1-3 or 3-5 V dc.  4-20 mA input can be calibrated 4-12 or 12-20 mA.

Maximum Input Common Mode Range +15 V to -5 V as measured from Terminal 11 to Terminal 13.

*Typical for most applications.

CALIBRATION

Содержание 42-103

Страница 1: ...80 0042 00 Rev 06 9 INSTRUCTION MANUAL 42 107 42 105 42 103 MODELS R E L E C T R I C A C T U A T O R S F O R I N D U S T R I A L P R O C E S S C O N T R O L...

Страница 2: ...ns 11 Calibration 12 Travel Limit Switch Adjustment 12 Setting Auxiliary Switches 14 Changing Direction of Travel 15 Feedback Signal 16 Demand Input Signal 18 Loss of Signal Function 19 Deadband Adjus...

Страница 3: ...ntenance Ideally suited for harsh industrial environments the Group 42 handles long stroke applications requiring up to 1 000 lbs 4 450 N of thrust The design employs a highly efficient ball screw cou...

Страница 4: ...ne current from a remote controller or manual switches 3 Modulating analog control option 7 Onboard actuator control electronics position output proportionally to mA Demand input signal Demand Input S...

Страница 5: ...adjustable Rated 10 A 125 150 Vac 5 A 125 Vdc 25 A 150 Vdc Handswitch Option 7 Permits local electrical operation independent of Demand input signal Handwheel Provides manual operation without electr...

Страница 6: ...7 11 279 28 19 32 726 46 19 32 1183 69 31 2 17 32 DIA 64 7 25 32 198 8 7 32 209 ALLOW 2 3 4 70 FOR REMOVAL 2 1 4 57 3 11 32 85 L DIMENSION 3 8 10 1 1 16 27 SEE TABLE REAR CLEVIS HOLE DIAMETER 1 25 SEE...

Страница 7: ...n conductive conduit and or cable trays All signal and power connections are made on the terminal board Typical wiring connections for each Group 42 control option are described on the following pages...

Страница 8: ...nal 12 The loop powered position feedback signal must be connected to a 2 wire type analog input that provides a dc voltage over the signal wires a dc voltage power supply must be wired in series with...

Страница 9: ...d to terminal 15 Direct AC Control with Actuator Powered Position Feedback Signal Customer must supply three wires to directly control the actuator motor direction One 120 V ac line to run Extend term...

Страница 10: ...m2 is recommended for this purpose CONDUIT ENTRIES Conduits are provided for power and signal wiring Temporary plugs are installed in the conduits at the factory for shipping only and are not intended...

Страница 11: ...put shaft travels through its desired stroke Note that the F extend and R retract LEDs on the control board light to indicate the direction of travel of the output shaft The LEDs remain lit when the u...

Страница 12: ...ine voltage and auxiliary switches are disconnected from external power sources Setting the Retract Travel Limit Switch S3 1 Remove the control module cover 2 Retract the output shaft to the desired t...

Страница 13: ...witch wires remove the two wires from the extend limit switch top switch and attach the meter across these contacts See Fig 3 at right Rotate the cam see Fig 2 at right until the meter shows no contin...

Страница 14: ...eter and actuator power 8 Extend Retract the output shaft again to the desired switch position If the contacts close the switch is properly set 9 Replace the control module cover SETTING AUXILIARY SWI...

Страница 15: ...to the power transformer see Figure 4 this page 3 For extend output shaft travel on an increasing signal the orange wire must be on the common terminal of S4 and the brown wire on the common terminal...

Страница 16: ...n TABLE 1 below FEEDBACK SIGNAL CALIBRATION For 4 wire feedback only All Group 42 actuators are shipped with the Option 7 Terminal Board Figure 5 TABLE 1 R4 F1 R3 VR2 VR1 TB1 TB2 22 4001 13 R 2 1 2 1...

Страница 17: ...put 14 Move the output shaft towards the maximum input signal position with a 249 ohm resistor To convert a 1 5 volt configuration to 4 20 milliamps remove the 249 ohm resistor and replace it with a 1...

Страница 18: ...sition if the travel is set to retract Allow the over travel limit switch to de energize the motor at the limit 16 Turn trim potentiometer R38 counterclockwise until the output signal is 20 05 mA 001...

Страница 19: ...n function in two ways 1 Actuator will stay in its last position when the signal was lost 2 Actuator will move to a position determined by the setting of trim potentiometer R16 The LOS function will s...

Страница 20: ...to stall will be decreased to 68 seconds which may be shorter than the full stroke travel time of some actuators R20 Parallel Resistor Effective Resistance Dead band 1 000 000 1 0 1 000 000 2 000 000...

Страница 21: ...he factory see back cover for factory contact information CUSTOMER KIT PART NUMBER Capacitor Replacement 6 0Nm 72 RPM Motor 60Hz 12 8064 10 Capacitor Replacement 6 0Nm 72 RPM Motor 50Hz 12 8064 20 Res...

Страница 22: ...itch failure a b c d Check control board calibration See calibration procedure p 18 Readjust limit switches See limit switch adjustment p 12 Restore input signal to actuator Replace limit switch Conta...

Страница 23: ...laims damages costs or liabilities including but not limited to attorney s fees and other legal expenses whether on account of negligence or otherwise except those claims based solely upon the neglige...

Страница 24: ...02 19 11 TERRY DRIVE NEWTOWN PENNSYLVANIA 18940 USA PHONE 215 968 4600 FAX 215 860 6383 E MAIL sales haroldbeck com www haroldbeck com HAROLD BECK SONS INC R Made in USA...

Отзывы: