Beck 42-103 Скачать руководство пользователя страница 19

19

80-0042-00, Rev. 06.9

Continued

FOR INSTALLATIONS WITH NO REMOTE 

INDICATOR: 

 Remove the resistor from between 

terminals 13 and 14 and connect the meter across 

these terminals.  Terminal 14 is positive.

  5. Connect 120 V ac to terminals 1 and 2.

  6. Turn on the 120 V ac power supply.

  7. Set the input signal to 100 percent, that is 20 

milliamps (5 volts) maximum.

  8. If the position feedback is less than 19.98 mA, 

then trim R13 clockwise.  If greater than 20.02 

mA, trim R13 counter-clockwise.  Trim R13 as 

required until the output signal is 20.000 mA ± 

.002 mA (5.00 V ± .50 mV).

   NOTE: As  the  output  signal  approaches 

20.00  mA,  R13  will  become  more  sensitive; 

at  that  point,  minor  adjustments  followed  by 

cycling the demand signal may be required to 

achieve the desired results.

   9. Set the input signal to zero percent, that is 4 

milliamps (1 volt).

 10. If the position feedback signal is greater than 

4.02 mA, then trim R14 counter-clockwise.  If 

less than 3.98 mA, trim R14 clockwise.  Trim 

R14  as  required  until  the  output  signal  is 

4.000 mA ± .002 mA (1.00 V ± .50 mV).

   NOTE: As  the  output  signal  approaches 

4.00  mA,  R14  will  become  more  sensitive; 

at  that  point,  minor  adjustments  followed  by 

cycling the demand signal may be required to 

achieve the desired results.

 11. Repeat Steps 7–10 as required.

 12. Calibration is complete.

 13. Replace the control module cover.

SETTING LOSS OF SIGNAL FUNCTION

Option 7 only

  The  Loss  of  Signal  (LOS)  feature  gives  the 

actuator  the  ability  to  move  the  output  shaft  to 

a predetermined position if the input signal falls 

below a predetermined value, as long as ac power 

is supplied. LOS can function in two ways:

 1.  Actuator will stay in its last position when the 

signal was lost.

 2.  Actuator will move to a position determined by 

the setting of trim potentiometer R16.

  The LOS function will start when the input signal 

falls below the level set by trim potentiometer R15.  

The range of adjustment for this input signal trigger 

level is from zero milliamps input to 8 milliamps (2 

volts).  The choice of having the actuator stay in 

place or move to a position is determined by the 

position of jumper plug J1/J2 on the control board.  

(J1 moves to a predetermined position, J2 stays 

in place).

  Unless otherwise specified at time of order,  Group 

42 actuators are shipped with the LOS input signal 

trigger level set to 3.4 milliamps (.85 volts). Jumper 

plug J1/J2 is set in the J2 or stay in place position.  

The move to position trim potentiometer (R16) is set 

so that if this function is chosen the actuator will move 

to the minimum input signal position.

NOTE:  The LOS position is adjusted relative to 

the feedback signal.  The feed back signal must 

be calibrated before the LOS can be set.

  Tools required for setting LOS: 

   

mA/V dc voltmeter

   

3/32 inch screwdriver

   

Large screwdriver

  Figure 7 shows the location of the jumper plug 

J1/J2 and the trim potentiometers R15 and R16 on 

the control board.  Figure 5, page 16, shows the 

location of test points TP1 and TP2.

1

F

R

1

A

1

1

1

M

1

CCW

CW

J1

J2

J6

J5

R20

FEEDBACK

POTENTIOMETER

S1

R16

S2

R14
R13

R15

R38

R46

P4

P4

R20

J3 / J4

J5 / J6

J1 / J2

S2 Toggle

(Automatic/Manual)

S1 Toggle

(Forward/Reverse)

1

J3
J4

FEEDBACK

POTENTIOMETER

1

1

CCW

CW

P4

P4

R16

R14
R13

R15

R38

R46

R20

1

J6

J5

1

J3
J4

1

J1

J2

1

F

R

A

1

M

S1

S2

R20

J3 / J4

J5 / J6

J1 / J2

S2 Toggle

(Automatic/Manual)

S1 Toggle

(Forward/Reverse)

22‑5001‑21

22‑4001‑17

Option 7 Control Boards

Figure 7

Содержание 42-103

Страница 1: ...80 0042 00 Rev 06 9 INSTRUCTION MANUAL 42 107 42 105 42 103 MODELS R E L E C T R I C A C T U A T O R S F O R I N D U S T R I A L P R O C E S S C O N T R O L...

Страница 2: ...ns 11 Calibration 12 Travel Limit Switch Adjustment 12 Setting Auxiliary Switches 14 Changing Direction of Travel 15 Feedback Signal 16 Demand Input Signal 18 Loss of Signal Function 19 Deadband Adjus...

Страница 3: ...ntenance Ideally suited for harsh industrial environments the Group 42 handles long stroke applications requiring up to 1 000 lbs 4 450 N of thrust The design employs a highly efficient ball screw cou...

Страница 4: ...ne current from a remote controller or manual switches 3 Modulating analog control option 7 Onboard actuator control electronics position output proportionally to mA Demand input signal Demand Input S...

Страница 5: ...adjustable Rated 10 A 125 150 Vac 5 A 125 Vdc 25 A 150 Vdc Handswitch Option 7 Permits local electrical operation independent of Demand input signal Handwheel Provides manual operation without electr...

Страница 6: ...7 11 279 28 19 32 726 46 19 32 1183 69 31 2 17 32 DIA 64 7 25 32 198 8 7 32 209 ALLOW 2 3 4 70 FOR REMOVAL 2 1 4 57 3 11 32 85 L DIMENSION 3 8 10 1 1 16 27 SEE TABLE REAR CLEVIS HOLE DIAMETER 1 25 SEE...

Страница 7: ...n conductive conduit and or cable trays All signal and power connections are made on the terminal board Typical wiring connections for each Group 42 control option are described on the following pages...

Страница 8: ...nal 12 The loop powered position feedback signal must be connected to a 2 wire type analog input that provides a dc voltage over the signal wires a dc voltage power supply must be wired in series with...

Страница 9: ...d to terminal 15 Direct AC Control with Actuator Powered Position Feedback Signal Customer must supply three wires to directly control the actuator motor direction One 120 V ac line to run Extend term...

Страница 10: ...m2 is recommended for this purpose CONDUIT ENTRIES Conduits are provided for power and signal wiring Temporary plugs are installed in the conduits at the factory for shipping only and are not intended...

Страница 11: ...put shaft travels through its desired stroke Note that the F extend and R retract LEDs on the control board light to indicate the direction of travel of the output shaft The LEDs remain lit when the u...

Страница 12: ...ine voltage and auxiliary switches are disconnected from external power sources Setting the Retract Travel Limit Switch S3 1 Remove the control module cover 2 Retract the output shaft to the desired t...

Страница 13: ...witch wires remove the two wires from the extend limit switch top switch and attach the meter across these contacts See Fig 3 at right Rotate the cam see Fig 2 at right until the meter shows no contin...

Страница 14: ...eter and actuator power 8 Extend Retract the output shaft again to the desired switch position If the contacts close the switch is properly set 9 Replace the control module cover SETTING AUXILIARY SWI...

Страница 15: ...to the power transformer see Figure 4 this page 3 For extend output shaft travel on an increasing signal the orange wire must be on the common terminal of S4 and the brown wire on the common terminal...

Страница 16: ...n TABLE 1 below FEEDBACK SIGNAL CALIBRATION For 4 wire feedback only All Group 42 actuators are shipped with the Option 7 Terminal Board Figure 5 TABLE 1 R4 F1 R3 VR2 VR1 TB1 TB2 22 4001 13 R 2 1 2 1...

Страница 17: ...put 14 Move the output shaft towards the maximum input signal position with a 249 ohm resistor To convert a 1 5 volt configuration to 4 20 milliamps remove the 249 ohm resistor and replace it with a 1...

Страница 18: ...sition if the travel is set to retract Allow the over travel limit switch to de energize the motor at the limit 16 Turn trim potentiometer R38 counterclockwise until the output signal is 20 05 mA 001...

Страница 19: ...n function in two ways 1 Actuator will stay in its last position when the signal was lost 2 Actuator will move to a position determined by the setting of trim potentiometer R16 The LOS function will s...

Страница 20: ...to stall will be decreased to 68 seconds which may be shorter than the full stroke travel time of some actuators R20 Parallel Resistor Effective Resistance Dead band 1 000 000 1 0 1 000 000 2 000 000...

Страница 21: ...he factory see back cover for factory contact information CUSTOMER KIT PART NUMBER Capacitor Replacement 6 0Nm 72 RPM Motor 60Hz 12 8064 10 Capacitor Replacement 6 0Nm 72 RPM Motor 50Hz 12 8064 20 Res...

Страница 22: ...itch failure a b c d Check control board calibration See calibration procedure p 18 Readjust limit switches See limit switch adjustment p 12 Restore input signal to actuator Replace limit switch Conta...

Страница 23: ...laims damages costs or liabilities including but not limited to attorney s fees and other legal expenses whether on account of negligence or otherwise except those claims based solely upon the neglige...

Страница 24: ...02 19 11 TERRY DRIVE NEWTOWN PENNSYLVANIA 18940 USA PHONE 215 968 4600 FAX 215 860 6383 E MAIL sales haroldbeck com www haroldbeck com HAROLD BECK SONS INC R Made in USA...

Отзывы: