Beck 42-103 Скачать руководство пользователя страница 12

12

80-0042-00, Rev. 06.9

NOTE:  Beck actuators are shipped ready 

for installation—no calibration or switch 

adjustments are required.  The procedures 

below are provided in the event that the 

application  requirements  are  different  from 

those originally specified.

CALIBRATION HIERARCHY

  The  calibration  hierarchy  provides  the 

chronological  order  for  performing  calibration 

procedures.  If, for some reason, any or all of the 

calibration procedures are required, they should be 

performed in the order outlined below:

STEP 1:  Adjust travel and auxiliary switches (see 

pages 12–14).

STEP 2:  Change direction of travel (see page 15).
STEP 3:  (Options 5 & 7 only).  Calibrate the position 

feedback output signal (see page 17).

STEP 4:  (Option 7 only) Calibrate the demand input 

signal (see page 18).

TRAVEL LIMIT SWITCHES (S3, S4)
 

  All Group 42 actuators are shipped from the 

factory with the travel limit switches (S3 and S4) 

adjusted  to  provide  the  full  rated  stroke  range 

unless a reduced stroke is specified at the time of 

order.  No adjustments are necessary unless the 

full stroke length needs to be shortened to meet 

different application requirements.

  The travel limit switches are labeled S3 and S4, 

and correspond to fully retracted and fully extended 

positions respectively.  These switches must be 

set  inside  the  mechanical  stop  limits  to  prevent 

the actuator from stalling against the mechanical 

stops.  Depending on the control option ordered, 

these switches serve slightly different purposes.

  Control option 3 (42-103):  S3 and S4 define 

the exact fully retracted and fully extended end of 

travel point.

  Control options 5 & 7 (42-105, 42-107):  S3 

and  S4  provide  electrical  over-travel  protection.  

In these versions, the control electronics position 

the output and determine the fully retracted and 

extended positions during normal operation.

CAUTION

Do not attach the meter or attempt 

to adjust the switch cams until the 

actuator is discon nected from the 

line voltage and auxiliary switches 

are disconnected from external 

power sources.

Setting the Retract Travel Limit 

Switch (S3)

  1.  Remove the control module cover.

  2.  Retract the output shaft to the desired travel 

limit.  For Options 3 & 5, skip to step 3.  For 

Option 7:  De-energize the motor by turning 

toggle switch S1 (see Fig. 3) to stop (center 

position).    Turn  the  Handwheel  until  the 

position  feedback  signal  (measured  across 

terminals 14 (+) & 13 (–)) decreases by .005 ± 

.001 mA (1.25 mV ± .25).  The .005 mA is the 

over-travel range.  NOTE: If direction of travel 

is set for retract on increasing demand, then 

turn  the  Handwheel  until  the  output  signal 

increases by .005 ± .001 mA (1.25 ± .25 mV). 

  3.  Disconnect the power from the drive.

 4. 

a.  For actuators with Option 3 or 5, connect 

the  continuity  meter  across  terminals  2 

and 9.  Rotate the cam (see Fig. 2 next 

page) until the meter shows an increase 

in  resistance  from  approx.  100  ohms  to 

more  than  1  M  ohms  (switch  contacts 

open, switch clicks).

    b.  For  actuators  with  Option  7,  remove  the 

cable tie holding the switch wires, remove 

the two wires from the retract limit switch 

(second  from  the  top),  and  attach  the 

meter across these contacts.  Rotate the 

cam  (see  Fig.  3  next  page  for  method 

only--shows S4 connected) until the meter 

shows  no  continuity  (switch  contacts 

open, switch clicks).

  5.  Disconnect  the  meter  and  reconnect  switch 

wires and actuator power.

  6. Extend the output shaft away from the retract 

travel limit.  Note the direction of rotation of the 

lobe of the cam.  The correct cam lobe motion 

is away from the switch lever and the switch 

lever should be on the lower part of the cam.  

If this is not correct, return to step 2 and reset 

the cam to the proper orientation. 

  7. Retract the output shaft to the desired travel 

limit.  If the desired stopping point is reached, 

the switch is properly set.

  8. For Option 7, redress the switch wires and secure 

to the control board standoff with a cable tie.

  9.  Replace the control module cover. 

S4

S3

CONTACTS CLOSED
CONTACTS OPEN

TRAVEL

LIMIT SWITCH

SETTINGS

For Option 5 & 7 Drives

switches are set .03” (±.01”)

beyond typical travel range 

0% FULLY

RETRACTED

100% FULLY

EXTENDED

CALIBRATION

Содержание 42-103

Страница 1: ...80 0042 00 Rev 06 9 INSTRUCTION MANUAL 42 107 42 105 42 103 MODELS R E L E C T R I C A C T U A T O R S F O R I N D U S T R I A L P R O C E S S C O N T R O L...

Страница 2: ...ns 11 Calibration 12 Travel Limit Switch Adjustment 12 Setting Auxiliary Switches 14 Changing Direction of Travel 15 Feedback Signal 16 Demand Input Signal 18 Loss of Signal Function 19 Deadband Adjus...

Страница 3: ...ntenance Ideally suited for harsh industrial environments the Group 42 handles long stroke applications requiring up to 1 000 lbs 4 450 N of thrust The design employs a highly efficient ball screw cou...

Страница 4: ...ne current from a remote controller or manual switches 3 Modulating analog control option 7 Onboard actuator control electronics position output proportionally to mA Demand input signal Demand Input S...

Страница 5: ...adjustable Rated 10 A 125 150 Vac 5 A 125 Vdc 25 A 150 Vdc Handswitch Option 7 Permits local electrical operation independent of Demand input signal Handwheel Provides manual operation without electr...

Страница 6: ...7 11 279 28 19 32 726 46 19 32 1183 69 31 2 17 32 DIA 64 7 25 32 198 8 7 32 209 ALLOW 2 3 4 70 FOR REMOVAL 2 1 4 57 3 11 32 85 L DIMENSION 3 8 10 1 1 16 27 SEE TABLE REAR CLEVIS HOLE DIAMETER 1 25 SEE...

Страница 7: ...n conductive conduit and or cable trays All signal and power connections are made on the terminal board Typical wiring connections for each Group 42 control option are described on the following pages...

Страница 8: ...nal 12 The loop powered position feedback signal must be connected to a 2 wire type analog input that provides a dc voltage over the signal wires a dc voltage power supply must be wired in series with...

Страница 9: ...d to terminal 15 Direct AC Control with Actuator Powered Position Feedback Signal Customer must supply three wires to directly control the actuator motor direction One 120 V ac line to run Extend term...

Страница 10: ...m2 is recommended for this purpose CONDUIT ENTRIES Conduits are provided for power and signal wiring Temporary plugs are installed in the conduits at the factory for shipping only and are not intended...

Страница 11: ...put shaft travels through its desired stroke Note that the F extend and R retract LEDs on the control board light to indicate the direction of travel of the output shaft The LEDs remain lit when the u...

Страница 12: ...ine voltage and auxiliary switches are disconnected from external power sources Setting the Retract Travel Limit Switch S3 1 Remove the control module cover 2 Retract the output shaft to the desired t...

Страница 13: ...witch wires remove the two wires from the extend limit switch top switch and attach the meter across these contacts See Fig 3 at right Rotate the cam see Fig 2 at right until the meter shows no contin...

Страница 14: ...eter and actuator power 8 Extend Retract the output shaft again to the desired switch position If the contacts close the switch is properly set 9 Replace the control module cover SETTING AUXILIARY SWI...

Страница 15: ...to the power transformer see Figure 4 this page 3 For extend output shaft travel on an increasing signal the orange wire must be on the common terminal of S4 and the brown wire on the common terminal...

Страница 16: ...n TABLE 1 below FEEDBACK SIGNAL CALIBRATION For 4 wire feedback only All Group 42 actuators are shipped with the Option 7 Terminal Board Figure 5 TABLE 1 R4 F1 R3 VR2 VR1 TB1 TB2 22 4001 13 R 2 1 2 1...

Страница 17: ...put 14 Move the output shaft towards the maximum input signal position with a 249 ohm resistor To convert a 1 5 volt configuration to 4 20 milliamps remove the 249 ohm resistor and replace it with a 1...

Страница 18: ...sition if the travel is set to retract Allow the over travel limit switch to de energize the motor at the limit 16 Turn trim potentiometer R38 counterclockwise until the output signal is 20 05 mA 001...

Страница 19: ...n function in two ways 1 Actuator will stay in its last position when the signal was lost 2 Actuator will move to a position determined by the setting of trim potentiometer R16 The LOS function will s...

Страница 20: ...to stall will be decreased to 68 seconds which may be shorter than the full stroke travel time of some actuators R20 Parallel Resistor Effective Resistance Dead band 1 000 000 1 0 1 000 000 2 000 000...

Страница 21: ...he factory see back cover for factory contact information CUSTOMER KIT PART NUMBER Capacitor Replacement 6 0Nm 72 RPM Motor 60Hz 12 8064 10 Capacitor Replacement 6 0Nm 72 RPM Motor 50Hz 12 8064 20 Res...

Страница 22: ...itch failure a b c d Check control board calibration See calibration procedure p 18 Readjust limit switches See limit switch adjustment p 12 Restore input signal to actuator Replace limit switch Conta...

Страница 23: ...laims damages costs or liabilities including but not limited to attorney s fees and other legal expenses whether on account of negligence or otherwise except those claims based solely upon the neglige...

Страница 24: ...02 19 11 TERRY DRIVE NEWTOWN PENNSYLVANIA 18940 USA PHONE 215 968 4600 FAX 215 860 6383 E MAIL sales haroldbeck com www haroldbeck com HAROLD BECK SONS INC R Made in USA...

Отзывы: