Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx
Page 61 of 260
Version: 25F
Max. total current (pn or pp)
8A
Auxilary outputs
24 VDC; 250mA (G.P.)
Digital I/O
01
– 05
24 VDC; 0,5A (G.P.)
06
– 10
Temperature rating
30°C
24 VDC; 2A (G.P.)
Temperature rating
50°C
24 VDC; 1,8A (G.P.)
Max. total current (I/O)
10A
Rated data
relays
Normally open
24 VDC; 2A (Pilot Duty
)
120 VAC; 2A (Pilot Duty
)
Normally closed
(Read back contact)
24 VDC; 2A (Pilot Duty
)
Environmental data
Temperature
0°C … +50°C operation
-
25C° … +70C° storage and transport
Class of protection
IP 20
Climatic category
3k3 acc. to DIN 60 721-3
Min-, Maximum relative humidity
(no condensation)
5% - 85%
EMC
EN 61000-6-2, EN 61000-6-4, EN 61000-6-7, EN
61800-3, EN 61326-3, EN 62061
Operating altitude
2000m
Overvoltage category
III
Degree of pollution
2
Mechanical data
Dimensions
(HxDxW [mm])
SMX132-0/2/D
= 100x115x67,5
SMX132-1/2/D
= 100x115x90
SMX132-0/R/2/D
= 100x115x90
SMX132-1/R/2/D
= 100x115x112,5
Weight
(g)
SMX132-0/2/D
= 400
SMX132-1/2/D
= 520
SMX132-0/R/2/D
= 500
SMX132-1/R/2/D
= 600
Mounting
To snap on top-hat rail
Number of T-bus connectors
SMX132-0/2/D
3
SMX132-1/2/D
4
SMX132-0/R/2/D
4
SMX132-1/R/2/D
5
Min. terminal cross-section / AWG
0,2 mm² / 24
Max. terminal cross-section / AWG
2,5 mm² / 12
(**)
pn/pp are configurable via SafePLC2
(***)
Derating, see Chapter „Derating outputs“
1)
Value applies only for extension module. For a total assessment in accordance with EN ISO 13849-1 one
must use a sries connection with the corresponding basic device
=> PFH
Logic
= PFH
Basic
+ PFH
Extension