
Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx
Page 249 of 260
Version: 25F
12.3.7 Verification software(program) and parameters
Verification takes place in two steps:
1. Checking the FUP with respect to the specified functionality.
2. Checking the FUP against the AWL-listing of the validation report, or the default
parameters against the one listed in the validation report.
12.3.7.1
Checking FUP
The programmed FUP must be compared with the defaults in the specification.
Note:
The comparison is all the more efficient the more clearly the programming has been
structured with respect to the safety functions.
Example:
Safety function:
1.1 Limitation of the max. travel speed of the carriage to 1.1 VMax
Monitoring of the maximum speed to < 1.1 VMax
FW Max Speed OK (ID 548) (is bridged by available gap):
FW Max Speed is permanently activated and responds when a speed of 550 mm/s is
exceeded.
Safety function:
Limitation of max. travel speed in carriage in the worker's area:
Monitoring of the maximum speed to < 0.33 m/s
Safe Speed OK (ID 2124) (is bridged by available gap):
Safe Speed OK responds when the the safe speed SLS (ID 2090) is exceeded in the
worker's area and during setup work.
Parameter SLS Safe Speed:
60 mm/s, no further parameters
Axis: 1
Setup
Axis: 1