Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx
Page 53 of 260
Version: 25F
Technical characteristic data SMX112/112A(/2/D)
Safety related characteristic data
Pl acc. to EN ISO 13849-1
PL e
PFH
1
)
/ Architecture
12,6 FIT
/Cat 4
SIL acc. to IEC 61508
SIL 3
Proof test interval
20 years = max. operation period
General data
Max. no. of expansion modules
-
Interface for expansion modules
Communication interface (/D) or
T-bus connector, pluggable in top-hat rail
Number of safe digital inputs
14 (OSSD capable)
Number of safe digital outputs
pn-switching
2
Number of safe digital I/O
-
Number of relay outputs
2
Number of safe analogue inputs
-
SMX112A/x
2 ****
Number of auxiliary outputs
2
Number of pulse outputs
(clock outputs)
2
Type of connection
Plug-in terminals with spring or screw connection
Axis monitoring
2
Encoder interfaces
(D-Sub / screw terminal)
2 / 2 *
Encoder technology
(See table encoder specifications)
1.
Encoder: SSI, SinCos, TTL, Proxi
2.
Encoder: HTL (200 kHz), SinCos (HiRes),
Resolver
SMXGen2 (/2)
Number of safe digital outputs
pn-switching **
2
pp-switching **
4
Electrical data
Supply voltage
(tolerance)
24 VDC; 3,15A
(-15%, +20%)
Fuse
X11.1
min. 30 VDC; max. 3,15A
Max. power consumption
(logic)
2,4W
Rated data digital inputs
24 VDC; 20mA, Typ1 acc. to EN 61131-2
Rated data digital outputs
pn-switching
24 VDC; 250mA
Auxiliary outputs
24 VDC; 250mA
Pulse outputs
(clock outputs)
24 VDC; 250mA
Rated data
relays
Normally open
DC13
AC15
24 VDC; 2A
230 VAC; 2A
Rated data analogue inputs
-
SMX112A/x ****
-
7 … +10V
4 … 20mA
SMXGen2 (/2)
Supply voltage
(tolerance)
24 VDC; 2A
(-15%, +20%)
Fuse
X11.1
min. 30 VDC; max. 3,15A
X11.2
min. 30 VDC; max. 10A
Max. power consumption
(logic)
4,7W
Rated data digital outputs
pn-switching
24 VDC; 2A ***
pp-switching
24 VDC; 2A ***
Electrical data (For UL only) SMXGen2 (/2)
Rated data digital outputs
pn-switching
Temperature rating
30°C
24 VDC; 2A (G.P.)
Temperature rating
50°C
24 VDC; 1,8A (G.P.)
pp-switching
Temperature rating
30°C
24 VDC; 2A (G.P.)
Temperature rating
50°C
24 VDC; 1,8A (G.P.)
Max. total current (pn or pp)
8A
Auxiliary outputs
24VDC; 250mA (G.P.)
Rated data
relays
Normally open
24 VDC; 2A (Pilot Duty
)
120 VAC; 2A (Pilot Duty
)