8 Safety related examination
In order to assure the reliability of the implemented safety functions the user must check and
document the parameters and links after the start-up and parameterization has taken place.
This is supported by the parameterization software SafePLC SMX100 (see programming
manual).
On the first page one can enter general system data. The last page of the validation report
contains individual evidence concerning the safety related examination.
Here the following entries are mandatory:
• Serial number (identical with the serial number on the type plate)
• Identity of the module
Here the responsible tester confirms that the CRC displayed in the programming desktop are
identical with the CRC stored in the SMX100 module.
Once all header data have been entered, the validation report can be generated by pressing the
control button "Save". The parameterization tool then creates a report
(.PDF) with the file name of the program data set. The report
contains the following information:
•
The 3 pages of header data edited above
•
The configuration of the encoder
•
The parameters of the existing monitoring function
•
The PLC program as instruction list
After the transmission of the configuration and program data to the SMX100 module the status
LED flashes yellow. This indicates that the configuration data have not yet been validated.
Pressing the button "LOCK CONFIGURATION" at the end of the validation dialog highlights the
data as "Validated" and the LED flashes in green.