4.3.5 Digital outputs
I/O’s (IQQx)
The modules
SMX100-2(/2), SMX100-4(/2)
SMX131(/2), SMX131R(/2), SMX131R-4/2
SMX132-x(R)/2/D
respectively have configurable safe digital I/O's in different numbers (see chapter 3 module
overview). This connection acts as safe digital pp-switching output parameterized as output
(IQQx).
4.3.5.1 Classification of the I/O
‘s (IQQx) when used as output
Classification
Achievable Pl
acc. to EN ISO
13849-1
Comment
Static single-channel
(2)
PL c
Fault detection or fault reaction acc. to cat. 2
Static two-channel
(2)
PL d
Same group(1):
-
Time-shifted triggering on PLC level
-
Fault approach short-circuit on both
outputs
Different group
(1)
:
-
Nom further requirements necessary
PL e
Different group
1)
required
Dynamically single-
channel
(2)
PL e
Nom further requirements necessary
Dynamically dual-
channel
(2)
PL e
No further requirements necessary
Note:
1) Group 1:
IQQ1
… IQQ6
Group 2:
IQQ7
… IQQ10
2) Static:
no pulse test on output
Dynamic:
Pulse test on output t
Test
≤ 500 µs