6 Installation
6.4.3 Connecting the appliance
Fig.15 Connection
NIE-B-057
Caution
Please ensure that the polarities shown on the terminals are
followed: live (L), neutral (N) and earth
4
.
1
Connect the connection cable already wired into the distribution board.
6.5 Filling the installation
Fig.16 Filling the tank
NIE-B-060
2
1
A
4
3
Once the hydraulic and electrical connections have been made:
1
Open a hot water tap.
2
Open the cold water tap to vent any air in the installation, ensuring
that valve
A
on the drain opening is properly closed.
3
The water heater starts to fill up and any air exits via the hot water
taps.
4
When the water overflows through the hot water tap, the tank is full.
5
Close all of the taps and check the pipes to make sure there are no
leaks.
Caution
If the water inlet pressure is lower than 0.15 MPa (1.5 bar), a
pump must be fitted to the water inlet. To guarantee the safe
use of the tank at a water inlet pressure of more than 0.65 MPa
(6.5 bar), fit a pressure reducer to the water inlet pipe.