Lock out (Status signals)
Status
signals
Description
Probable causes
Checking / solution
Error code 4
(4 times red
signal)
Fan fault
4
External draught over the
boiler
4
Defective gas/air unit
4
Check for adequate draw on the chimney connection
4
Replace the gas/air unit
Error code 5
(5 times red
signal)
Parameter error
4
Bad connection
4
Safety parameters not
found
4
Check the wiring
4
ResetdF/dU code with
Recom
software, controller or
service tool
Error code 6
(6 times red
signal)
Miscellaneous
4
Several possible causes
4
The fault codes can be read with the
Recom
service
software, a suitable controller or a service tool
Lock out (Error code -
e[KK
)
Error
code
Description
Probable causes
Checking / solution
e[00
Storage unit PSU
parameter not found
4
Bad connection
4
Check the wiring
e[01
The safety parameters
are incorrect
4
Bad connection
4
PSU defective
4
Check the wiring
4
Replace PSU
e[02
Flow temperature
sensor short circuited
4
Sensor not or badly
connected
4
Bad connection
4
Sensor fault
4
Check the wiring
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Replace the sensor if necessary
e[03
Flow temperature
sensor open circuit
4
Sensor not or badly
connected
4
Bad connection
4
Sensor fault
4
Check the wiring
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Replace the sensor if necessary
e[04
e[05
Flow temperature too
low
Flow temperature too
high
4
No circulation
4
Bad connection
4
Sensor not or badly
connected
4
Sensor fault
4
Vent the air in the heating system
4
Check the water pressure
4
Check the wiring
4
Check the circulation (direction, pump, valves)
4
Check the cleanliness of the heat exchanger
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Replace the sensor if necessary
e[06
Return temperature
sensor short circuited
4
Sensor not or badly
connected
4
Bad connection
4
Sensor fault
4
Check that the sensor has been correctly fitted
4
Check the wiring
4
Check that the sensors are operating correctly
e[07
Return temperature
sensor open circuit
4
Sensor not or badly
connected
4
Bad connection
4
Sensor fault
4
Check that the sensor has been correctly fitted
4
Check the wiring
4
Check that the sensors are operating correctly
e[08
e[09
Return temperature too
low
Return temperature too
high
4
No circulation
4
Bad connection
4
Sensor not or badly
connected
4
Sensor fault
4
Vent the air in the heating system
4
Check the water pressure
4
Check the wiring
4
Check the circulation (direction, pump, valves)
4
Check the cleanliness of the heat exchanger
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Replace the sensor if necessary