5.5.6.
Connecting the safety valve discharge pipe
1. Connect the safety valve pipe to the safety valve outlet
ê
.
CAUTION
4
Any soldering must be completed before fitting the
pipework to prevent damage from heat.
4
Do not fit the condensate trap until the discharge pipe
has been soldered and fitted.
5.5.7.
Connecting the condensate discharge pipe
The condensate trap is supplied separately as standard with the
boiler (Includes flexible plastic drain hose and adapter). Fit these
parts underneath the boiler. To do this, proceed as follows:
1. Fill the condensate trap with water up to the mark.
CAUTION
Fill the condensate trap with water before starting the
boiler to avoid combustion products escaping from the
boiler.
2. Press the condensate trap firmly into the
j
opening provided for
it underneath the boiler. The condensate trap must click into place.
CAUTION
Check whether the condensate trap is solidly fitted in the
boiler.
3. Insert the flexible drain hose from the condensate trap into a drain
pipe.
4. Mount a trap or a siphon in the discharge pipe.
CAUTION
Do not make a permanent rigid connection owing to
maintenance work on the condensate trap.
4
Do not plug the condensate discharge pipe.
4
Do not drain condensation water into a roof gutter at
any time.
4
Connect the condensate discharge pipe in
accordance with prevailing standards.
R000739-A
1
R000740-A
1
2
3
5. Installation
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
26
02092014 - 7619497-02