When choosing the position for mounting the boiler, bear
in mind the authorised position of the combustion gas
discharge outlets and the air intake opening.
¼
For more information, see chapter: "Connections for
the air and exhaust pipes", page 29.
)
For more detailed information, see: Flue Accessories
& Fitting Guide.
WARNING
4
Fix the appliance to a solid wall capable of bearing
the weight of the appliance when full of water and fully
equipped.
4
Do not place the appliance above a heat source or a
cooking appliance.
4
Do not locate the boiler in direct sunlight.
4
It is forbidden to store inflammable products and
materials in the boiler room or close to the boiler,
even temporarily.
CAUTION
4
The boiler must be installed in a frost-free
environment.
4
An earthed electrical connection must be available
close to the boiler.
4
A connection to the mains drainage system for the
discharge of condensate must be available close to
the boiler.
n
Safety rating
Z
Zones
OZ
Breakdown of the exterior zone
B
Bathtub or shower tray
For safety rating IP X4D, installation in the bathroom is possible in
zones 2 and 3 and in the breakdown of the exterior zone.
In this case, connect the 230 V power supply as a fixed connection
to a fused spur.
CAUTION
In the case of a fixed connection to the power cord, you
must always install a main bipolar switch with an opening
gap of at least 3 mm (EN 60335-1).
T000756-A
Z
OZ
1
0
B
2
3
60
225
240
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
5. Installation
02092014 - 7619497-02
21